Operating instructions

www.pulsar.pl EN54-2A17LCD RED POWER
16
6.4.2. LCD screen – current parameters .
To set the screen, press the „ESC” button, use the „<or „>” buttons to choose the icon and press the
„SET” button to confirm.
The screen displays electrical parameters and the status of the technical outputs during operation.
Illumination of an element informs about an activation and reflects the status of LEDs on the PCB of the PSU (see
Table 1, [10]).
Fig 10. LCD panel – PSU parameters.
Table 8. The description of the screen symbols - current parameters of the PSU.
Screen field Description
Additional information
- 230V AC power ON
(highlighted = AC power on)
See section 7.2.4
- Battery charging indication
(highlighted = battery charging)
- PSU overload indication
(highlighted = PSU overload)
- Indication of exceeding the „Imax a” current
(flashing = „Imax a” exceeded)
See section:
6.10,
6.11
- PSU failure indication
(highlighted = PSU failure)
See sections:
6.4.6
6.5
- Battery failure indication
(highlighted = battery failure)
See sections:
6.4.6
6.5
- EXTi input status indication
(highlighted = EXTi input activated)
See sections:
6.4.6
6.6
Current electrical parameters of the PSU:
U
AC
– mains supply voltage (230V AC)
U
BAT
– battery voltage
T
BAT
– battery temperature
R
BAT
– resistance of the battery circuit
U
AUX1
– AUX1output voltage
U
AUX2
– AUX2 output voltage
I
AUX
– total output current
See section:
6.4.4
The status of the technical outputs:
EPS - AC power indication
open= AC power failure
closed = AC power – O.K.
PSU – PSU failure indication
open= PSU failure
closed = PSU working correctly O.K.
APS – battery failure indication
open= battery failure
closed = battery O.K.
ALARM – collective failure indication
open= failure
closed = O.K.
EXTo – relay output status indication
See sections:
6.4.6
6.5
TAMPER input status (highlighted = activated)
See section:
6.7