4.3. Description of components and power supply terminals.
Table 1. Components of the Power supply PCB (Fig. 2).
Co
mpo
nent
No.
Description
[1] PANEL – optical indication connector
[2]
BUZZER – acoustic
indication (section 7.2.2)
[3]
V
EXT
jumper
– polarization of the EXTi circuit
(section 6.6)
[4]
F
BAT
– fuse in the battery circuit,
F5A / 250V
[5]
F
AUX1
– fuse in the AUX1 output circuit,
F4A / 250V
[6]
F
AUX2
– fuse in the AUX2 output circuit,
F4A / 250V
[7] SERIAL communication port
[8]
Z2 jumper temporary lock of the battery test
(section 8.5)
[9]
OVP – overvoltage protection optical indication
(section 6.9)
[10]
LEDs – optical indication:
AC AC power
AUX1 – AUX1 output voltage
AUX2 – AUX2 output voltage
OVL – PSU overload
APS battery failure
PSU – PSU failure
ALARM – collective failure
EXTi – EXTi input status
EXTo – EXTo relay output status
LB – battery charging
[11]
Terminals:
~AC~ – AC power input
EPS FLT – technical output of AC power failure indication
open = AC power failure
close = AC power - O.K.
PSU FLT – technical output of PSU failure indication
open = failure
close = PSU operation - O.K.
APS FLT – technical output of battery failure
open = battery failure
close = battery status - O.K.
ALARM – technical output of collective failure
open = failure
close = O.K.
EXTo – controlled relay output
EXTi – input of collective failure
+BAT- battery power output
+AUX1- AUX1 power output
(+AUX1= +U, -AUX=GND)
+AUX2- AUX2 power output
(+AUX2= +U, -AUX=GND)
[12} TAMPER – antisabotage protection microswitch connector (section 6.7)
[13] Connector– for connecting the EMC filter
Fig. 2. The view of the PSU’s PCB.