User Instructions

www.pulsar.pl EN54C RED POWER plus
22
Table 5. Mechanical parameters.
Battery space:
2x7 Ah
2x17 Ah
2x28 Ah
2x40 Ah
2x65 Ah
Enclosure dimensions
W=330, H=305, D+D
1
=82+8
W
1
=335, H
1
=308 [+/- 2mm]
W=385, H=402, D+D
1
=88+8
W
1
=390, H
1
=406 [+/- 2mm]
W=420, H=407, D+D
1
=178+8
W
1
=425, H
1
=411 [+/- 2mm]
W=410, H=648, D+D
1
=180+8
W
1
=416, H
1
=652[+/- 2mm]
Mounting (WxH)
303x230 xΦ6 x4szt [mm]
358x325 xΦ6 x4szt [mm]
388x380 xΦ6 x4szt [mm]
378 x 570 xΦ6 x4szt [mm]
Fitting battery
(WxHxD) (max.)
2x7 Ah/12 V (SLA)
315x100x75 [+/-2 mm] max
2x17 Ah/12 V (SLA)
375x180x80 [+/-2 mm] max
2x28 Ah/12 V (SLA)
405x175x170 [+/-2 mm]
2x40 Ah/12 V (SLA)
405x175x170 [+/-2 mm]
2x65 Ah/12 V (SLA)
360x190x170 (x2) [+/-2 mm]
Enclosure
Steel plate DC01 1mm
Steel plate DC01 1,2mm
Steel plate DC01 1,5mm
color: RAL 3001 (red)
Closing
Key lock
Terminals
Battery outputs BAT: 6,3F-
0,75
Battery outputs BAT: Ф6 (M6-0-2,5)
Mains supply: Ф0,41÷2,59 (AWG 26-10), 0,5÷4mm
2
Outputs: Ф0,51÷2,05 (AWG 24-12), 0,5÷2,5mm
2
Cable glands
PG9 cable diameter Ф4÷8mm
PG11 cable diameter Ф5÷10mm
Notes
The enclosure does not adjoin the mounting surface so that cables can be led.
Convection cooling.
Table 6. Safety of use.
Protection class EN 60950-1:2007
I (first)
Protection grade EN 60529: 2003
IP30
Insulation electrical strength:
- between input (network) circuit and the output circuits of the PSU
- between input circuit and protection circuit
- between output circuit and protection circuit
3000 V AC min.
1500 V AC min.
500 V AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500 V DC