Data Sheet

Table Of Contents
SPECIFICATION
30W Ultra Slim Step Shape DIN Rail
HDR-30 series
HDR-30-5
HDR-30-12
HDR-30-15 HDR-30-24
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INPUT
INRUSH CURRENT (Typ.)
SAFETY STANDARDS
WORKING HUMIDITY
WORKING TEMP.
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
OVERLOAD Note.4
OVER VOLTAGE
5V
12V
15V 24V
3A
2A
2A 1.5A
0 ~ 3A
0 ~ 2A
0 ~ 2A 0 ~ 1.5A
15W
24W
30W 36W
80mVp-p
120mVp-p
120mVp-p 150mVp-p
±2.0%
±1.0%
±1.0% ±1.0%
±1.0%
±1.0%
±1.0% ±1.0%
±1.0%
±1.0%
±1.0% ±1.0%
500ms, 50ms/230VAC 500ms, 50ms/115VAC at full load
30ms/230VAC 12ms/115VAC at full load
47 ~ 63Hz
82%
88%
89% 89%
0.88A/115VAC 0.48A/230VAC
COLD START 25A/115VAC 45A/230VAC
105 ~ 160% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
Protection type : Shut down o/p voltage, re-power on to recover
-30 ~ +70 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85, 10 ~ 95% RH non-condensing
±0.03%/ (0 ~ 50) RH non-condensing
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
968.1K hrs min. MIL-HDBK-217F (25)
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
ENVIRONMENT
PROTECTION
SAFETY &
EMC
(Note 5)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC
I/P-O/P:100M Ohms / 500VDC / 25/ 70% RH
HDR-30-48
48V
0.75A
0 ~ 0.75A
36W
240mVp-p
±1.0%
±1.0%
±1.0%
90%
13.5 ~ 18V 21.6 ~ 29V10.8 ~ 13.8V
4.5 ~ 5.5V
43.2 ~ 55.2V
5.75 ~ 7.5V
15 ~ 18V 18.8 ~ 22.5V 30 ~ 36V
57.6~ 67.2V
85 ~ 264VAC (277VAC operational ) 120 ~ 370VDC (390VDC operational )
OPERATING ALTITUDE
2000 meters
UL60950-1, U 508, TUV EN61558-2-16 IEC60950-1 a EN50178,L , pproved; Design refer to TUV EN60950-1
EN55024, EN55035, EN61000-6-2, EN61204-3
EMC IMMUNITY
EMC EMISSION
Parameter
Conducted
Radiated
Harmonic Current
Voltage Flicker
Standard
EN55032(CISPR32)
EN61000-3-2
Test Level / Note
Class B
-------
EN61000-3-3
Class B
Class A
Parameter
ESD
Radiated Susceptibility
EFT/Burest
Surge
Standard
EN61000-4-2
Test Level /Note
Level 3, 8KV air; Level 2, 4KV contact, criteria A
Level 4,2KV/L-N, criteria A
Conducted
Magnetic Field
EN61000-4-3
EN61000-4-4
EN61000-4-6
EN61000-4-5
EN61000-4-8
EN61000-4-11
Voltage Dips and interruptions
Level 3, criteria A
Level 3, criteria A
Level 3, criteria A
Level 4, criteria A
EN55032(CISPR32)
File Name:HDR-30-SPEC 2017-05-03
DIMENSIONOTHERS
NOTE
PACKING
35*90*54.5mm (W*H*D)
0.12Kg;96pcs/12.5Kg/1.04CUFT








95% dip 0.5 periods, 30% dip 25 periods,
95% interruptions 250 periods
μμ