TECHNICAL DATA
Nominal voltage: 12V
Nominal capacity: 18Ah / C *
20
Projected lifespan: 5 ÷ 8 years at 20°C
Internal resistance:
The charging voltage at 25°C:
Buffer operation 13,5 ÷ 13,8 V (-18mV/°C)
Cyclic operation 14,4 ÷ 14,9 V (-30mV/°C)
Charging current:
Recommended 1,8
Maximum 5,4 A
The maximum discharge current (5s): 270 A (5 sec.)
Weight: ~ 5,2 kg
Dimensions: W=182, H=168, D=77 [mm, +/-2]
Warranty: 1 year
Notes: maintenance-free battery, made with AGM technology
*-
- during charging 0°C ÷ 40°C
- during discharge -15°C ÷ 50°C
- during storage -20°C ÷ 40°C
A
see technical drawing above
the actual capacity at 20 h discharge
15 m
The permissible operating temperature range:
Terminals:
contains lead
Sealed Lead Acid Maintenance Free Batteries
of the HPB series
Pulsar
®
HPB18-12
18Ah/12V HPB battery
v.1.0/I
CODE:
NAME:
HP
utomation systems
B batteries are maintenance-free Valve Regulated Lead Acid Batteries with self-regulating one-sided
safety valves and internal gas recombination.
The batteries are made in AGM (Absorbent Glass Mat) technology; the electrolyte is held in the glass
mat. The technology used allows installing batteries in places with natural (gravity) ventilation and minimizes
maintenance.
They are dedicated for devices requiring emergency power to a load when the input power source or
mains power fails, such as:
· Power supply for fire alarm systems: EN54 series
· Power supply I&HAS: PSBEN series
· Voice alarm systems (VAS): DSOP24V
· Security systems (CCTV, I&HAS, ACC)
· UPS
· A
APPLICATION:
Phone +48-14-610-19-40, Fax: +48-14- 610-19-50, www.pulsar.pl, www.zasilacze.pl, E-mail: sales@pulsar.pl
EN
Dimensions [mm]
+/- 2mm;Tolerance:
Pole terminals
182
77
168
12
2
ø5,5