User Instructions

1
PS-1001270
PS 12V/7A enclosed switch mode power supply
PL
Edition: 10 from 01.03.2018
Supersedes: 9 from 27.05.2014
EN
Features:
power output 7A/12÷15V DC
*
wide range of mains supply: 176÷264V
high efficiency 83%
LED indication
protections:
SCP short-circuit protection
OVP overvoltage protection
overvoltage protection
overload protection (OLP)
warranty 2 year from the production date
1. Technical description.
1.1. General description.
The power supply unit is intended for supplying power to alarm system devices requiring 12V DC supply voltage and
current load of I=7A. The design enables simple change of the output voltage, within the range of 12V÷15V DC, by means of a
potentiometer. The power supply unit is protected against short-circuit, overload and overvoltage.
1.2. Specifications.
Mains supply
176 ÷ 264V AC; 50÷60Hz
Current consumption
0,8A@230V AC max.
Supply power
100W max.
Efficiency
83%
Output voltage
12V DC
Output current t
AMB
<30°C
7A - see chart 1.
Output current t
AMB
=40°C
5A - see chart 1.
Voltage adjustment range
12V ÷ 15V DC
Ripple
100mV p-p max.
Short-circuit protection SCP
electronic, automatic recovery
Overload protection OLP
105-150% of power supply, automatic recovery
Surge protection
varistors
Overvoltage protection OVP
>16V (automatic return)
LED indication
green LED indicates DC voltage
Operating conditions
2-nd enviromental class, temperature: -10
o
C ÷ +40
o
C
relative humidity 20%...90%, without condensation
Dimensions
L=199, W=98, H=38 [+/- 2mm]
Net/gross weight
0,57kg / 0,62kg
Protection class PN-EN 60950-1:2007
I (first) requires a protective conductor (PE)
Connectors
power-supply: Φ0,63-2,50 (AWG 22-10)
outputs: Φ0,63-2,50 (AWG 22-10)
Electrical strength of insulation:
- between input (network) circuit and output circuits of
the PSU (I/PO/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit
(O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC
Storage temperature
-20ºC...+60ºC
Vibrations and impulse waves during transport
according to PN-83/T-42106
* In order to extend the life of the power supply, the load current of 5A is recommended.
*
See graph 1.