User Manual
www.pulsar.pl Seria PSG2
6
Models
PSG2-24V2A
PSG2-24V3A
PSG2-24V5A
PSG2-24V10A
PSU type
A (EPS - External Power Source), II environmental class
Supply voltage
~ 200 - 240 V
Current consumption
0,8 A
1 A
1,3 A
1,5 A
Power frequency
50/60 Hz
Inrush current
40 A
60 A
PSU power
69 W
96 W
138 W
276 W
Output current (max.)
2,5 A
3,5 A
5 A
10 A
Efficiency
89%
89%
89%
87%
Output voltage
22 – 27,6 V – buffer operation
20 – 27,6 V – battery-assisted operation
Ripple voltage (max.)
100 mV p-p
Current consumption by the PSU
systems during battery-assisted
operation
20 mA
30 mA
40 mA
40 mA
Fitting battery
7 – 17 Ah
7 – 40 Ah
7 – 40 Ah
7 – 65Ah
Charging current (jumper
selectable)
I1: 0,5 A
I2: 1 A
I1: 0,5 A
I2: 1 A
I1: 1 A
I2: 2 A
I1: 1 A
I2: 2 A
I3: 4 A
Net/gross weight
0,38 / 0,42 [kg]
0,39 / 0,45 [kg]
0,81 / 0,86 [kg]
1,23 / 1,30 [kg]
Battery circuit protection SCP and
reverse polarity connection
- glass fuse F
BAT
(in case of a failure, fuse-element replacement
required - under power supply cover)
- glass fuse F
BAT
( in case of a failure, fuse-element replacement
required )
Overload protection OLP
105-150% PSU power, automatically recovered
Overvoltage protection OVP
>37 V (activation requires disconnecting the load or supply for about approx. 1 min)
Deep discharge battery protection
UVP
U<19 V (± 5%) – disconnection of battery terminal
Optical indication
- LEDs on PCB of power supply unit
LED optical indication output
(intended for optional indication set
PKAZ168)
LED AC – presence of AC voltage
LED DC – presence of DC voltage in the output of the PSU
APS FLT – battery failure
Fuses: - F
BAT
F 3,15A/250V
T 6,3A/250V
F 8A/250V
T 10A/250V
Enclosure dimensions (LxWxH)
[±2mm]
159x98x42
159x98x42
204x141x52
237x168x54
Terminals:
Mains supply:
Outputs:
Battery outputs:
0,5 – 2,5 mm
2
(AWG 26 – 12)
Battery wires 6,3F – 45cm, angle muffs ML062
Battery wires Ф6 (M6-2,5), 45cm
Optional equipment:
a set for optical indication LED PKAZ168, mounting plate DIN3-4
Notes:
Convectional cooling
Forced cooling