User Instructions

www.pulsar.pl RCB48V RACK POWER
5
Mechanical parameters (Table 3).
Mounting dimensions
W=19”, H=2U, D=425
Dimensions
W=483, W
1
=435, H=88, D=425, D
1
=15 [+/- 2mm]
Mounting
Six-point butt mounting to RACK profiles - a set of 6 M6 screws + cage nuts included
Net/gross weight
5,2kg / 5,9kg (without batteries)
Enclosure
Steel plate 1,2 mm, color RAL 9005
Connectors
Battery inputs: 6,3F-2,5
The BAT output: Φ0,63÷2,50 (AWG 22-10) 0,5-2,5mm
2
The ALARM output: Φ0,5-2,1 (AWG 24-12) 0,5-1,5mm
2
Operation parameters (Table 5)
Environmental class
II
Operation temperature
-10ºC...+40ºC, ensure free air flow around the enclosure
Storage temperature
-20ºC...+60ºC
Relative humidity
20%...90%, no condensation
Sinusoidal vibrations during operation:
Unacceptable
Surges during operation
Unacceptable
Direct insolation
Unacceptable
Vibrations and surges during transport
According to the PN-83/T-42106 standard
2. Mounting.
2.1. Requirements.
The enclosure should be mounted by a qualified installer, holding relevant (applicable and required for a
given country) permits and licenses for low-voltage installations. The device shall be mounted in confined spaces
(in accordance with the 2nd environmental class) with normal air humidity (RH=90% max. without condensation)
and the temperature from -10°C to +40°C. In order to meet the requirements of LVD and EMC directives, the rules
for power supply, enclosures, shielding, and cable routing, depending on application, must be observed.