Data Sheet
ROUPS48V v.1.0/II
ROUPS 54V/5A RACK mounted buffer power supply.
CODE:
TYPE:
DESCRIPTION
The ROUPS48V buffer power supply unit is designed for uninterrupted power supply of requiring stabilized
voltage of 48V DC (+/- 15%). The PSU provides voltage of U=54V DC current efficiency max. I=4,5A + 0,5A battery
charge. In case of power decay, a battery back-up is activated immediately. The PSU output protected
independently with melting fuse 5 . The power supply is fitted with the ALARM output of collective failure. In case of
failure, relay contacts are switched automatically, which is accompanied by acoustic and optical indication (the
corresponding led goes on). The power supply construction is based on the switch mode PSU with high energy
efficiency and is located in an enclosure adapted for mounting in standard RACK 19” cabinets.
AUX power supply output can be split into 8 or 16 outputs with the use of RACK fuse modules:
- the RLB8 (RACK 8x2A fuse modules)
- the RLB16 (RACK 16x1 fuse modules)
A
EN
wyjście TAMPER : przewody 30cm
Tel. +48-14-610-19-40, fax: +48-14- 610-19-50, www.pulsar.pl, e-mail: sales@pulsar.pl
RACK series power supply unit
RACK mounted buffer power supply
Features:
· DC 54V/5A* uninterruptible power supply
· outputs protected by 5A melting fuse
· wide range of mains supply AC: 176÷264V AC
· high efficiency 85%
· built-in power factor correction system (PFC)
· battery charging and maintenance control
· excessive discharging (UVP) protection
· battery output protection against short circuit and
reverse connection
· battery charge current: 0,5A
(batteries 4x7Ah / 4x17Ah)
· control of voltage presence at the outputs
· acoustic indication of failure
· LED optical indication: AC, DC, TEMP, LoB,
ALARM, AUX
· the ALARM technical output of collective failure
– relay type, activated by:
· 230V AC power loss
· low voltage of the PSU (<46V)
· activation of the output fuse
· too high temperature of the PSU (>70°C)
· the PSU failure
· protections:
· SCP short-circuit protection
· OVP overvoltage protection
· overvoltage protection
· overload protection OLP
· forced cooling (fan)
· warranty – 2 year from the production date
D
1
W
H
D
D
2
W
1