ROUPS48V v.1.0 ROUPS 54V/5A RACK mounted buffer power supply. EN Edition: 2 from 30.03.2017 Supercedes the edition: 1 from 02.12.
www.pulsar.
www.pulsar.pl ROUPS48V RACK POWER 1. Technical description. 1.1. General description. The ROUPS48V buffer power supply unit is designed for uninterrupted power supply of requiring stabilized voltage of 48V DC (+/- 15%). The PSU provides voltage of U=54V DC current efficiency max. I=4,5A + 0,5A battery charge. In case of power decay, a battery back-up is activated immediately. The PSU output protected independently with melting fuse 5A.
www.pulsar.pl ROUPS48V RACK POWER Fig. 2. The front power of the power supply unit. Fig.3. The view of the PSU. 1.4. Specifications. - electrical parameters (tab.2) - mechanical parameters (tab.3) - operation safety (tab.4) - operating parameters (tab.5) Electrical parameters (tab. 2).
www.pulsar.pl RACK POWER ROUPS48V Mechanical parameters (tab. 3).
www.pulsar.pl ROUPS48V RACK POWER 2.2. Installation procedure. 1. Before installation, cut off the voltage in the 230V power-supply circuit. 2. Mount the power supply in a RACK 19" cabinet as shown below: - Mount M6 cage nuts - Secure the enclosure with 4xM4 screws 3. Connect the receivers’ cables to the terminals AUX. 4. If needed, the following technical connections can be made: - ALARM – technical output of collective failure 5.
www.pulsar.pl ROUPS48V RACK POWER 3.2. Technical output. The power supply is fitted with the ALARM output of collective failure (relay type). A collective failure can be triggered by the following events: - 230V AC mains power failure - Activation of the glass fuse FAUX - Failure of the switch mode power supply - Too high temperature of the switch mode power supply (>70°C) - Low battery voltage (<46V) Fig. 4. Electrical diagram of the ALARM collective output of failure. CAUTION! In Fig.
www.pulsar.pl RACK POWER ROUPS48V WEEE LABEL Waste electrical and electronic equipment must not be disposed of with normal household waste. According to the European Union WEEE Directive, waste electrical and electronic equipment should be disposed of separately from normal household waste. CAUTION! The power supply unit is adapted for a sealed lead-acid battery (SLA). After the operation period it must not be disposed of but recycled according to the applicable law.