User Instructions

4
Table 3. Electrical parameters
230V AC (-15%/+10%) / 50Hz
1,3A / 230VAC max.
219W
16 x 0,6A ΣI=4A (max.)
54V DC
250mA
0,5A max. /4x12V (+/-5%)
5h 15min
melting fuse
U<38V (± 5%) – disconnect of connection battery
Table 4. Mechanical parameters
Mounting dimensions
W=19”, H=2U, D=348
Dimensions
W=482, W
1
=446, H=88, D=348, D
1
=32, D
2
=15 [+/- 2mm]
Net/gross weight
5,6 / 6,5 kg
Enclosure
Steel plate, DC01 1,0mm color: black RAL 9005
Fixation
four-point butt mounting to RACK profiles the set include 4 M6 screws + cage nuts
Connectors
Power supply of the cameras: RJ45 socket
Output of recorder: RJ45 socket or SFP
Outputs: Φ 0,63-2,50 (AWG 22-10), battery output BAT: 6,3F-2,5
Notes
Forced cooling (fan).
Table 5. Operation safety
Protection class PN-EN 609501:2007
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Electrical strength of insulation:
- between input and output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC
Declarations
CE
Table 6. Operating parameters
-10ºC...+45ºC
-20ºC...+60ºC
20%...90%, without condensation
unacceptable
unacceptable
unacceptable
According to PN-83/T-42106