User Instructions

User manual
for
STB, SCB, and HPB maintenance-free
batteries.
Version No: 1 of 11.05.2018
Replaces version: --------------
EN
General information:
The: STB, SCB, and HPB batteries are maintenance-free Valve Regulated Lead Acid Batteries with self-
regulating one-sided safety valves and internal gas recombination. The batteries are made in AGM (Absorbent Glass
Mat) technology; the electrolyte is held in the glass mat. The technology used allows installing batteries in places with
natural (gravity) ventilation and minimizes maintenance. To ensure long and safe use of the battery, follow the
instructions in the manual.
Health and safety recommendations:
All work on the battery should only be carried out by a qualified person with appropriate qualifications.
Before starting work, remove rings, necklaces, watches and other metal objects.
Use appropriate protective measures such as glasses, gloves, protective clothing, and extinguishing agents.
Do not touch the metal parts of the batteries directly; all work on the battery should only be carried out using
insulated tools.
The battery should not be placed in sealed enclosures that do not provide adequate ventilation, because in
the case of improper operating parameters or unfavorable conditions, flammable gases may be released from
the battery, which may lead to explosion.
The possibility of shorting the positive (+) and negative (-) terminals of an individual battery or a battery pack,
even if discharged, must be strictly prevented.
Extreme caution should be taken when connecting batteries in series, because the total voltage can be
dangerously high.
Do not disassemble the enclosure and safety valves.
If the battery housing is damaged (cracks or damaged cover safety valves), the battery needs to be replaced;
prevent electrolyte leakage and dispose the battery.
Storage:
The batteries should be stored in a dry and cool place with an efficient ventilation system, away from heat, fire,
sunlight, and metal elements. The recommended storage position is to set the battery terminals facing up. The storage
temperature should be between -10°C ÷ 40°C. Due to the self-discharge phenomenon, check the battery charge level
once every three months and recharge when needed. If the battery is stored at a temperature above 25°C, the charge
level should be checked more often. This is due to the fact that the self-discharge increases with increase in temperature.
The battery must be recharged if the voltage at the terminals is lower than 12.54V (2.09V for a single cell), which is
equivalent to about 80% of the nominal capacity.
Installing the batteries:
Before installing the battery, it must be inspected for mechanical damage; check the polarity, condition of
connections, and terminals. Do not mix batteries of different types or which have different usage history, as this may
damage the batteries or shorter their life. The batteries cannot operate with terminals facing down, because the adverse
conditions can activate the safety valves and the electrolyte may leak out of the housing. The recommended position is to
set the battery terminals facing up. In order to ensure good ventilation, a distance of approx. 10mm ÷ 20mm is to be kept.
Operation:
The batteries operate at a temperature of 0°C ÷ 40°C; maintain the recommended temperature range of 20-25°C
to ensure the longest lifespan. Every 8°C increase in operating temperature will cause the battery life reduce by 50%
Sealed VRLA batteries must not be too deeply discharged (the minimum discharging voltage can be determined on the
basis of discharge characteristics in the data sheet) and cannot be discharged because each time a lead acid battery is
discharged, it sulfates, which results in an irreversible capacity loss and reduced service life. The battery should be

Summary of content (2 pages)