User manual

Pulse Catch Input
Mode 50
UP Counters
Installation and
Safety Guidelines
7–8
Pulse Catch Input
DL205 High Speed Counter
Interface Manual, 2nd Ed, Rev. A
The following RLL example shows how to set the Pulse Catch Input, Mode 50, in
V–memory location V7633.
DirectSOFT32 Display
LD
K50
SP0
Load Mode 50 in Accumulator
OUT
V7633
Transfer Contents of
Accumulator to V7633
Two commands are needed to put the values into V-memory. The value must first be
loaded into the accumulator of the CPU, then the CPU must transfer the value to the
memory location. In this case, 50 is to be placed in V7633. This value is loaded into
the accumulator, LD K50. The CPU then writes this data to the memory location
V7633, once it reads the OUT command, OUT V7633. Notice that an SP0 contact is
used in this rung. This relay is on for the first scan only. This will load the values into
memory initially, thereby keeping the scan time to a minimum.
Up to four(4) pulse catch inputs can be used with the DL240/250–1/260 CPUs and
one (1) pulse catch input for the DL230 CPU. The following steps will discuss the
programming for each channel which has an interrupt device wired to it.
The table below gives a description for each of the V-memory locations that must be
configured for each I/O point which are selected to have high speed interrupt
capability.
V–Memory Description
V7633 Primary Mode (Pulse Catch=50)
V7634 Point 00
V7635 Point 01
V7636 Point 02
V7637 Point 03
Step 2:
How Many Pulse
Catch Inputs
Step 3:
Configure the
V-Memory