Technical data
Active / passive The CP 5430 TF/CP 5431 FMS must be active.
Network file Here, the local system is assigned to a network. The
network is managed independently of the database. As
the default, the name of the last network processed is
displayed. The assignment to a network is necessary to
establish a consistent bus parameter field in all the
databases belonging to the network using the menu
item Network -> Network Matching.
(Range of values: alphanumeric characters and the
period format: xxxxxNCM.NET, only the characters in
the name marked with x are freely selectable. If you
type in more characters, a message is displayed.)
SIMATIC details:
Base SSNR: The value corresponds to the address of page 0 (range
of values: 0 to 248 in steps of 4)
.
No. of interfaces: This parameter specifies how many interfaces (pages)
can be addressed. (Range of values: 1 to 4)
Informative parameters:
Submodule size: Memory capacity of the submodule in Kilobytes (range
of values: 16, 32, 64).
Example: "Submodule type: EPROM Submodule size:
32 Kb".
Recommended submodule size:
16 Kbytes for PLC links and for access to layer 2
services
64 Kbytes for TF applications
☞
You can change the submodule size with the appropriate
utility (see Section 15.2)
Basics of Configuration B8976060/02
Volume 1 6 - 22