Technical data
The group identifier makes it possible to distinguish the following 8 groups.
If no group identifier was specified at the HDB call for the global control job
(all bits set to "0"), the global control job is sent and executed by all DP
slaves capable of the Sync and/or freeze mode.
If the group identifier is not zero, the conditions for execution are as follows:
– Sync and/or freeze mode must be supported by the DP slave.
– At least one group of the global control job and of the group
identifier must match.
Slave name: Here, it is possible to assign up to 10 ASCII characters
long to the slave for documentation purposes.
Check slave
sync mode/
Check slave
freeze mode:
If you select the ON mode here, the CP checks
whether or not the slave supports the Sync. or Freeze
jobs using the parameter assignment frame during start
up.
1st group
2nd group
3rd group
8th group
0
:
:
0 0 0 0 0
0
0
Fig. 11.16 Group Identifier Structure
Distributed I/Os (DP) B89060/02
Volume 1 11 - 28