Technical data
Highest min.
slave interval
The time specified here is the highest value of the
minimum slave interval of all DP slaves to be
processed using the DP polling list.
The min. slave interval of a DP slave is the time the
slave requires to process the last polling frame
received. Following this, the slave is ready to receive
the next polling frame.
The value of the min. slave interval can be found in the
documentation for the particular slave.
Clear DP:
Yes:
The output data of the CPU are only transferred
when all the DP slaves are in the cyclic data transfer
phase. Otherwise, all the output data are sent as "0".
No:
The output data of the CPU are transferred as
soon as the slave is in the cyclic data transfer phase.
Output fields:
L2 address and
name:
Here, all the configured L2-DP slaves are listed with
their bus address and name.
Function keys:
F1
LINE +
Move display one line forwards.
SHIFT F1
PAGE +
Move display one page forwards.
F2
LINE -
Move display one line backwards.
SHIFT F2
PAGE -
Move display one page backwards.
Distributed I/Os (DP) B89060/02
Volume 1 11 - 34