Technical data
ET200U-DP example of a configuration
The following I/O assignments were made with the help of the COM for the
ET200U-DP station 10 described below:
I/O area editor:
DP-mode: cycle-synchronized
Input area DP STA: PY100 Input area DP-END: PY107
Output area DP STA: PY80 Output area DP-END: PY85
DP-Editor:
Station 10, Input area: PY100 to 107/Output area PY80 to PY85
ET200U-DP
Station 10
Occupied address area (bytes)
I peripheral byte
address assignment
Q peripheral byte
address assignment
11241 14
PY80
PY100
PY101
PY81
PY102 PY103
PY82
PY83
PY84
PY85
PY104
PY105
PY106
PY107
2) The bytes be handled in the user program
as being word size (e.g. PY82 and PY83 = PW82).
This is only guaranteed in the "cycle-synchronized" mode
1) Number of channels used can be selected
In this case 2.
PS
IM
318B
DQ
440
DQ
441
DI
422
AQ
470
DI
430
DI
421
AI
464
empty
1)
2)
2)
2)
2)
Table 11.2 ET200U-DP Example of a Configuration
Distributed I/Os (DP) B89060/02
Volume 1 11 - 36