Technical data

Bits
8-11 Meaning
0
H
No error
If bit 3 "job complete with error" is nevertheless set, this means that the CP has
set up the job again following a cold restart or RESET.
1
H
Wrong type specified in block call (QTYP/ZTYP).
2
H
Memory area does not exist (e.g. not initialized)..
3
H
Memory area too small.
The memory area specified in the HDB call (parameters Q(Z)TYP, Q(Z)ANF,
Q(Z)LAE) ist for too small for the data transmission.
4
H
Timeout (QVZ).
Acknowledgement from the memory cell is absent during data transfer. Remedy:
check and if necessary replace the memory submodule or check and correct the
source/destination parameters.(types AS, PB and OY specified).
5
H
Incorrect parameters assigned to status word.
The parameter "ANZW" was specified incorrectly. Remedy: correct the
parameter or set up the data block correctly in which the ANZW is to be located.
(DB-No. and DB length).
6
H
Invalid source/destination parameter.
Parameter ID "NN" or "RW" was used or the data length is too small (=0) or
longer than 128 bytes. Remedy: use the correct Q(Z)TYP parameter; "NN" and
"RW" are not allowed for this type of data transmission.
7
H
Local resource bottleneck.
There are no data buffers available for processing the job. Remedy: retrigger
the job, reduce the CP load.
B
H
Handshake error.
The HDB processing was incorrect or the HDB monitoring time was exceeded.
Remedy: start the job again.
C
H
System error.
Error in the system program. Remedy: inform Siemens service
D
H
Disabled data block.
The data transmission is or was disabled during the HDB processing. (control bit
disable/ enable in status word disable).
E
H
Free
F
H
Job or "channel not programmed.
programming error or wrong (SSNR/ANR). Remedy: program ANR as "channel"
(FREE) or correct SSNR/ANR in HDB call
Table 12.3 Error Bits (bits 8...11) in the Status Word
B8976060/02 Service and Diagnostics using FMA Functions
12 - 11 Volume 1