Technical data

DP station
status:
Local DP master mode with the following meaning:
RUN: DP polling list is processed.
STOP: DP polling list is not processed.
Clear: DP polling list is processed, all output data bytes
are sent with the value "0".
DP station
L2 add:
Bus address of the DP master (CP).
DP station
poll. cyc. timeout:
An asterisk indicates that the DP polling list could not
be processed in the set time.
Cycl. global
control from PLC:
An asterisk indicates that a cyclic
global_control control command is currently being
processed.
Sel: Indicates with an asterisk that a line is selected.
Slave address: Bus address of the DP slave.
Name: The names of the DP slaves specified in parameter
assignment are displayed here.
Vendor ID: The configured vendor identifier of the DP slave is
shown here.
Group ID: The group ID of the DP slave specified in parameter
assignment is displayed here.
Pass.: An asterisk here indicates that there is no parameter
assignment for this slave (neither an input nor output
area was specified in the DP editor).
Transfer: An asterisk here indicates that this slave is in the cyclic
data transfer phase with the master.
Diagn.: An asterisk here indicates that there are new diagnostic
data from the slave.
Documentation, Test B8976060/02
Volume 1 14 - 30