9.9 Testing Air Dryer Fan
NOTE: To test the fan, the cabinet temperature must be above 90 F.
9.9.1 Place your hand outside the
Dryer to feel for air being
blown outwards.
NOTE: The fan will turn OFF when the cabinet temperature is below 80 F.
If the fan is not blowing air outwards as described:
Verify the cabinet temperature is above 90
F.
Check for loose wiring. Refer to the Wiring Diagram (section 14.1 )
Replace defective fan (see sections 11.1 for part detail and 11.5 for
ordering information).
Replace defective control board if fan does not respond properly to
temperature changes (see sections 11.1 for part detail and 11.5 for
ordering information).
9.10 Testing Compressor ON/OFF Cycling
9.10.1 When the Unit Screen
(8.5.5.1 ) appears on the
display, press the HOLD
Button on the Front Panel to
freeze that screen.