User`s guide
PUREGAS, LLC P550W Series Air Dryers User’s Guide
Page 96 of 99 P011658 – Rev. M
14.3 SNMP Parameters
Device Configuration Information
Device ID Alphanumeric (Defined by Customer)
Device Model Alphanumeric (Factory Preset)
Device Firmware Version Numeric (Factory Preset)
Current Date/Time Numeric (mm/dd/yy hh:mm)
IP Address Numeric (xxx.xxx.xxx.xxx)
Subnet Mask Numeric (xxx.xxx.xxx.xxx)
Gateway Address Numeric (xxx.xxx.xxx.xxx)
SNMP Trap Server Address Numeric (xxx.xxx.xxx.xxx)
Status Readings (Read-Only)
Outlet Pressure Reading Numeric (PSI)
Tank Pressure Reading Numeric (PSI)
Humidity Reading Numeric (%)
Flow Reading Numeric (SCFD)
Cabinet Temperature Reading Numeric (DEG F)
Compressor Total Run Time Reading Numeric (Hours)
Compressor Last Run Time Reading Numeric (Seconds)
System Status ON / SHUTDOWN
Compressor Status ON / OFF
Fan Status ON / OFF
Heater Status (Outdoor Unit Only) ON / OFF
Alarm Readings (Read-Only)
High Flow Alarm OK / Alarm
High Outlet Pressure Alarm OK / Alarm
Low Outlet Pressure Alarm OK / Alarm
High Humidity Alarm OK / Alarm
High Cabinet Temperature Alarm OK / Alarm
High Compressor Last Run Time Alarm OK / Alarm
Maintenance Required Alarm OK / Alarm
Total Alarm OK / Alarm
Configuration Settings (Read-Write)
High Flow Alarm Threshold Numeric (SCFD)
High Outlet Pressure Alarm Threshold Numeric (PSI)
Low Outlet Pressure Alarm Threshold Numeric (PSI)
High Humidity Alarm Threshold Numeric (%)
High Compressor Last Run Time Alarm Threshold Numeric (Seconds)
Reset Compressor Total Run Time Reading Numeric (Hours)
Start Up Delay Numeric (Seconds)
Alarm Delay ON / OFF
Alarm Traps Sent to SNMP Server
High Flow
High Outlet Pressure
Low Outlet Pressure
High Humidity
High Cabinet Temperature
High Compressor Last Run Time
Maintenance Required
Total Alarm