Instruction manual
Hallett 30 1” Instruction Manual 
Released on 1-May-14 – X800058P  Page 18  UV Pure Technologies Inc. © 2014 
water, unplug the unit until the water supply can be restored. In the event of a 
power failure, the unit will shut down and the solenoid valve will close, preventing 
water from flowing. When the power returns, the unit will automatically restart 
and perform a self-test. If no faults are detected, the unit will return to normal 
operation and the solenoid valve will open. Note that even during a brownout, the 
supply voltage may drop low enough to cause the unit to shut down. If the unit 
does not automatically restart as described above, unplug the unit and plug it in 
again. 
Step 1: Plug the unit into the Transient Voltage Surge Suppressor. Connect the 
surge protector to a GFCI. Flip the switch on the Transient Voltage Surge 
Suppressor to ON position to start the lamps. Caution: Never look into or place 
any exposed skin into the illuminated areas when the unit is operating. 
Step 2: Once the unit is plugged in, all three lights will illuminate and an audible 
alarm will sound. This verifies that the lights and the alarm are functioning. The 
unit then performs a self-test. During this test, the alarm continues to beep and 
the solenoid valve remains closed. The green light illuminates when the UV 
lamps have reached full power and there are no system faults. New lamps may 
take from a few moments to several hours to reach full power. Continue to 
run the unit until the lamps reach full power. The optional solenoid valve will 
then open and allow water to flow through the unit. This is the normal operating 
mode of the unit. If the unit fails to start, unplug the unit and plug it in again. 
Avoid continuously starting and stopping the unit within a 24 hr period, as this will 
accelerate the aging of the UV lamps. 
The self-cleaning feature of the Hallett system involves a wiper turning inside the 
quartz sleeve. The wiper operates either upon power up of the unit or shortly 
afterwards and then periodically afterwards. Pushing the Reset button for 1 
second will also cause the wiper to operate for several minutes. 
Seasonal Use and Shutting Down of Unit 
Unplug the unit during extended periods of no water usage (four days or more), 
as in the case of seasonal residences or during a vacation. If the possibility of 
freezing exists, the unit and any filters must be drained. (See Draining the Unit.) 
Upon returning, reconnect all fittings, close all valves and turn on water supply. 
Plug in the Hallett and when operational, flush the water through the unit for at 
least 5 minutes. 
Caution: When the unit is not operating, the solenoid valve remains closed. If the 
solenoid valve is forced open or if the optional bypass piping is used, untreated 
water may enter the plumbing system. Emergency use of untreated water is the 
only situation where the bypass piping should be used. Any water used for 
drinking should be boiled. Unplug the unit if the bypass is used. Do not run the 
unit dry. This will cause potential damage and scratching of the quartz 
sleeve. 
Disinfecting the Plumbing 
Disinfection of the household or facility plumbing should be performed after the 
Hallett has been installed and is operating. This procedure should also be done if 










