Technical data

PVI 1800/PVI 2500(Rev A) Installation and Operation Manual
32
DOCR-070570-A
Overview error codes
Code Designation Condition Solution
101
Hardware error, internal
communication interrupted
The inverter resumes feeding the grid
when automatic switching on of the
inverter reconnects it with the grid
The service technician should be
informed if this error code has been
seen repeatedly or continuously
203 Grid frequency too high
The inverter switches to normal
power/feed mode as soon as the grid
frequency returns to its nominal value
Check grid frequency
The service technician should be
informed if this problem occurs on a
regular basis
204 Grid frequency too low
The inverter switches to normal
power/feed mode as soon as the grid
frequency returns to its nominal value
Check grid frequency
The service technician should be
informed if this problem occurs on a
regular basis
205 Extreme grid over-voltage
The inverter switches to normal
power/feed mode as soon as the grid
voltage returns to its nominal value
Check grid voltage
The service technician should be
informed if this problem occurs on a
regular basis
206 Grid over-voltage
The inverter switches to normal
power/feed mode as soon as the grid
voltage returns to its nominal value
Check grid voltage
The service technician should be
informed if this problem occurs on a
regular basis
207 Grid under-voltage
The inverter switches to normal
power/feed mode as soon as the grid
voltage returns to its nominal value
Check grid voltage
The service technician should be
informed if this problem occurs on a
regular basis
208 Extreme grid under-voltage
The inverter switches to normal
power/feed mode as soon as the grid
voltage returns to its nominal value
Check grid voltage
The service technician should be
informed if this problem occurs on a
regular basis
301
Internal fault on the device
or
blown GFDI fuse
The inverter switches off
Check the GFDI fuse
Please contact your installer/service
technician or Solectria Renewables. We
recommend switching off the inverter to
prevent any damage occurring to it.
Note:
this condition can occur during
operation in weak sunlight. See page 31
302 Excessively high temperature
The inverter switches off and switches
back into power feed mode when the
temperature has dropped to the normal
operating temperature
Check to ensure that the inverter is not
subject to direct sunlight. Please
observe the description of mounting.
Please contact your installer/service
technician or Solectria Renewables if
this measure does not eliminate the fault
506 Ground fault current > than 0.8 A The inverter switches off Check installation