Technical data

PVI 1800/PVI 2500(Rev A) Installation and Operation Manual
39
DOCR-070570-A
Output (AC) specifications for PVI 1800/PVI 2500 Inverter:
PVI 1800 PVI 2500
Continuous AC output power 1800 Watts AC 2500 Watts AC
Operating voltage range +/- 10% 240/208V AC 240/208V AC
Operating frequency range 59.3 to 60.5 Hz 59.3 to 60.5 Hz
Maximum Continuous Output Current
7.5A @ 240V AC
8.65A @ 208V AC
10.4A @ 240V AC
12A @ 208V AC
Maximum Continuous Output Power
1800 Watts AC
@ 208 & 240 VAC
2500 Watts AC
@ 208 & 240 VAC
Total Harmonic distortion (THD)
(@ full power)
< 5% < 5%
Power Factor > 97% > 97%
Anti-islanding protection per UL1741/IEEE1547 per UL1741/IEEE1547
Ground fault protection NEC 690-5 NEC 690-5
Over current protection inverter limited inverter limited
Short circuit protection per UL1741/IEEE1547 per UL1741/IEEE1547
Surge test per UL1741/IEEE 62.41 per UL1741/IEEE 62.41
Inverter peak Efficiency* 94.1 % 94.2 %
Other specifications:
LCD Display Included Included
Pre-wired AC & DC (PV) Connections Included Included
Ambient Temperature
-4
o
to 140
o
F
(-20
o
to 60
o
C)
-4
o
to 140
o
F
(-20
o
to 60
o
C)
Temperature for full power operation
-4
o
to 131
o
F
(-20
o
to 55
o
C)
-4
o
to 131
o
F
(-20
o
to 55
o
C)
Storage Temperature
-40
o
to 173
o
F
(-40
o
to 70
o
C)
-40
o
to 173
o
F
(-40
o
to 70
o
C)
Cooling Passive (PVI 1800) Fan (PVI 2500)
Enclosure NEMA 4, IP-65 NEMA 4, IP-65
Weight 34.2 lb. (15.5 kg) 36.4 lb. (16.5 kg)