Specifications

V97-600002 Page 11 of 31
2.3.4 GFI Circuit
The purpose of the Ground Fault Interrupter (GFI) circuit is to detect a ground fault
(unintended current flow from the PV arrays to earth ground).
For the GFI circuit to function as designed, the PV array safety ground must
be connected only at the ground terminals provided.
Bonding the safety ground to the grounded leg of the array anywhere but
through the inverter will bypass the GFI circuit. This creates an unsafe
operating condition.
The GFI works by using a fuse to connect or bond the PV array negative (or
the PV array positive if using a positively grounded array) to earth ground
through the 1 A fuse.
If current is greater than 1 A between the grounded array terminal and the
earth ground, the fuse will “blow”. A “blown” or open fuse will disconnect the
PV arrays from their ground reference and interrupt the ground fault current.
In this situation, the inverter will cease operation and display a fault message
(as illustrated below):
Fault 0400 0000
Ground Fault
If the inverter displays “Ground Fault”, turn OFF the AC and DC to the
inverter and refer to the Troubleshooting section of this manual.
Figure 5: AC and PV Grounding
AC Ground
PV Ground