Specifications
V97-600002 Page 7 of 31
Figure 2: Inverter with mounting bracket in place
NOTE: Leave the inverter cover off to allow for electrical connections described in
Section 2.3.
2.3 Electrical Connections
CAUTION:
1. The National Electrical Code (NEC) requires that the inverter be connected to
a dedicated circuit with no other outlets or devices connected to the same
circuit. See NEC Section 690-64(b)(1). The NEC also places limitations on
the size of the inverter and the manner in which it is connected to the utility
grid. See NEC Section 690-64(b)(2).
See Table 2.1 for more information on required branch circuit protection.
2. To reduce the risk of fire, connect the inverter to the appropriate size breaker
(See Table 2.1). Maximum branch-circuit over-current protection calculated
in accordance with the National Electrical Code (NEC), ANSI/NFPA 70.
Inverter model Circuit breaker
required
PVP 1100 1 pole 15 A
PVP 2000 2 pole 15 A
PVP 2800 2 pole 20 A
PVP 3000 2 pole 20 A
Table 2.1Required Branch Circuit Protection