Table 6‑16. Inverter model number
Inverter Model Modbus Model Number
PVP30kW 0272, 0273, 0274, 0288, 0289, 0290
PVP35kW 0300, 0301, 0302, 0303
PVP50kW 0304, 0305, 0306, 0307
PVP75kW 0276, 0277, 0278, 0279
PVP100kW 0280, 0281, 0282, 0283
PVP250kW 0312, 0313, 0314, 0315, 0316, 0317, 0318, 0319
PVP260kW 0312, 0313, 0314, 0315, 0316, 0317, 0318, 0319
PVP500kW 0386, 0387
Table 6‑17. Bit mapping for inverter configuration register
Inverter Configuration Bit Mapping Instructions
AC volts = 208 0x0001
AC volts = 240 0x0002
AC volts = 480 0x0004
AC volts = 600 0x0200
Transformer tap position 0x0008
This bit is:
Set if the tap is at 265 V
Clear if the tap is 295 V
The default is 295 V.
Transformer wiring
configuration
0x0010
This bit is:
Set if the inverter is wired
as delta
Clear if the inverter is
wired as wye
The default is wye.
Utility meter installation
flag
0x0100
This bit is:
Set if the meter is installed
Clear if the meter is not
installed
The default is not installed.
Advanced Energy