Table 6‑19. Modbus status and fault code registers
Description Start
Register
End
Register
No. of
Registers
Modbus
Address
Data
Type
Notes
Modbus base address = 2000
Inverter
operating
status (state)
2100 2100 1 42101 UINT See Table 620 on
page 627.
Main fault 2101 2101 1 42102 UINT See the fault
codes descriptions
in the inverter
troubleshooting
information.
Drive fault 2102 2102 1 42103 UINT See the fault
codes descriptions
in the inverter
troubleshooting
information.
Voltage fault 2103 2103 1 42104 UINT See the fault
codes descriptions
in the inverter
troubleshooting
information.
Grid fault 2104 2104 1 42105 UINT See the fault
codes descriptions
in the inverter
troubleshooting
information.
Temperature
fault
2105 2105 1 42106 UINT See the fault
codes descriptions
in the inverter
troubleshooting
information.
System fault 2106 2106 1 42107 UINT See the fault
codes descriptions
in the inverter
troubleshooting
information.
System
warnings
2107 2107 1 42108 UINT See the fault
codes descriptions
in the inverter
troubleshooting
information.
PVM (PV
Monitoring)
status codes
2108 2108 1 42109 UINT See Table 621 on
page 627.
Advanced Energy
6‑26 Data Monitoring and Controls 570-1001792-05A