Table 9‑2. Electrical specifications (Continued)
Description Specification
MPPT range
Note 2
PVP250kW and PVP260kW: 295 V to 595 V
PVP260kW-LV: 265 V to 595 V
Maximum voltage at open circuit
600 V
OC
Startup voltage
PVP250kW and PVP260kW: :330 V
PVP260kW-LV model: 300 V
Startup power
PVP250kW: 1800 W
PVP260kW and PVP260kW-LV models: 1800 W
Note 1
Information also known as the maximum fault current contribution.
Note 2
At unity power factor and nominal AC voltage.
Table 9‑3. Utility interconnect voltage and frequency trip limits and times
Voltage and Frequency Trip Limits and Times
The default trip limits and times meet UL1741 anti-islanding requirements.
Voltage trip limit field adjustment range as a percentage of nominal: –12% to +10%
Accessible range of frequency trip times: 0.16 s to 300 s
Accessible range of low frequency setting (Hz):
Adjustable low trip 57.5-59.8 Hz
High trip fixed at 60.5 Hz
(The accuracy limit of time measurement is ± 0.1 s.)
480 VAC Configurations
Condition
Factory Setting
(VAC) Range (VAC)
Default Trip Time
(seconds)
Voltage phase high 304.8 304.8 to 332.5 1.0
Voltage phase low 243.9 216.1 to 243.9 2.0
Voltage phase fast high 332.5 332.5 0.16
Voltage phase fast low 138.6 138.6 0.16
600 VAC Configurations
Condition
Factory Setting
(VAC) Range (VAC)
Default Trip Time
(seconds)
Voltage phase high 381.1 381.1 to 415.7 1.0
Voltage phase low 304.8 270.2 to 314.8 2.0
Voltage phase fast high 415.7 415.7 0.16
Voltage phase fast low 173.2 173.2 0.16
Advanced Energy® PVP250kW and PVP260kW Inverters
570-1001792-05A Specifications A‑3