INVERTER MONITORING
The inverter is equipped with a data monitoring module that can be used to monitor
the inverter through one of the following interfaces:
Basic performance data can be accessed using a free web-based monitoring
service provided by AE.
Locally through a third party monitoring system using Modbus/TCP or
Modbus/RTU.
Related Links
“Data Monitoring and Controls” on page 61
CALCULATING DC INPUT VOLTAGE
To Calculate Maximum Open Circuit Voltage
Calculate the maximum open circuit (no load) voltage for each series module
connection. Refer to the Advanced Energy Solar Energy web site and select the
String Calculator to calculate the input from the PV array.
Contact AE Solar Energy Technical Support if you require assistance
calculating the maximum DC input voltage for your array at your specific
location.
Important
Each DC input connection must be wired to deliver the same input voltage.
Important
For all temperature conditions, the open circuit voltage for each series
connection must be less than or equal to 600 VDC.
DC SUBCOMBINER OPTIONS
The inverter comes with standard positive and negative bus bars for landing DC
inputs from the PV array.
Advanced Energy® PVP250kW and PVP260kW Inverters
570-1001792-05A Planning 3‑7