PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect INSTALLATION & OPERATION MANUAL 97-600100-02-A01
Preface PV Powered Contact Information PV Powered, Inc. PO Box 7348 Bend, OR 97708 Tel: 541-312-3832 Technical Support: 1-877-312-3832 Fax: 541-383-2348 www.pvpowered.com email: support@pvpowered.com Document Copyright PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual ©2009 PV Powered. All rights reserved. This manual may not be reproduced or distributed without written permission from PV Powered.
ii
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual Safety Information and Conventions SAVE THESE INSTRUCTIONS: This manual contains important instructions for the PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect that shall be followed during installation and maintenance of the inverter.
For applicability of technical information with your specific product, contact PV Powered Customer Service and Technical Support at support@pvpowered.com. Certifications UL 1741 IEEE 1547 FCC Class A & B CEC Efficiency Testing CSA 22.2 107.
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual Acronyms and Abbreviations AC Alternating Current ANSI American National Standards Institute AWG American Wire Gage CEC California Energy Commission (US)/Canadian Electrical Code CSA Canadian Standards Association CPU Controlled Processing Unit DC Direct Current EGC Equipment Grounding Conductor FCC Federal Communications Commission (US) GEC Grounding Electrode Conductor GFI Ground Fault
vi
Table of Contents Preface.................................................................................................................. i Safety Information and Conventions.................................................................. iii Acronyms and Abbreviations...............................................................................v 1. Introduction and Safety....................................................................................1 1.1 Introduction..............................
Appendix A - Specifications................................................................................43 A.1 Inverter Specifications.............................................................................43 A.2 Integrated AC/DC Disconnect Specifications.........................................45 A.3 Circuit Breaker Requirements.................................................................46 A.4 Abnormal Specifications.........................................................................
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual List of Figures and Tables Figure 2-1 Interior Components of the Inverter/Disconnect Unit................6 Figure 3-1 Figure 3-2 Figure 3-3 Figure 3-4 Small Mounting Bracket............................................................7 Large Mounting Bracket............................................................8 Inverter’s Inside Screw Below the Power Board.......................
Table A-1 Table A-2 Table A-3 Table A-4 Inverter PVP1100 through PVP2800 Specifications................43 Integrated AC/DC Disconnect Technical Specifications..........45 Circuit Breaker Requirements..................................................46 Abnormal Specifications..........................................................46 Figure B-1 Figure B-2 Figure B-3 Figure B-4 Figure B-5 Figure B-6 Figure B-7 Figure B-8 Inverter’s Power Board Terminals...........................................
1. Introduction and Safety 1.1 Introduction The PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect is a utility interactive inverter for photovoltaic (PV) systems. The inverter and disconnect are integrated, requiring installation as a single unit. The integrated inverter and disconnect are tied to an electrical source provided by the local utility company as well as the PV system.
! CAUTION • • • • ! All electrical installations should be done in accordance with local electrical codes and the National Electrical Code (NEC), ANSI/NFPA 70. Before connecting the inverter to the electrical utility grid, your utility company must grant approval. Only qualified electricians should make the connection. When exposed to light, PV arrays form electrical energy that creates a potentially hazardous condition.
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual ! ! CAUTION Read all safety warnings and instructions before installing or operating the inverter/disconnect unit. ATTENTION Lire toutes les alertes de sécurité et les instructions avant d’installer ou d’utiliser l’onduleur ou le dispositif de déconnexion.
4
2. Planning 2.1 Selecting a Location for the Inverter and Integrated AC/DC Disconnect When choosing a location for the inverter/disconnect unit, consider the following criteria: • • • • The unit is suitable for both indoor and outdoor installation; the inverter and disconnect enclosures have a NEMA 3R rating. The optimum location of the unit is outside, shielded from direct exposure to sunlight (i.e. not on the south facing side of the building). The heat sink temperature can exceed 158°F (70°C).
The large bracket: • Has two top screw holes at either end of the large bracket, 16” (40.6 cm) apart which are designed to match standard stud spacing. Refer to Figure 3-2. The inverter also has an internal mounting screw. Refer to Figure 2-1 for the location of this screw. ! ! WARNING Before drilling holes to mount the inverter, verify that there are no electrical wires or plumbing in the area.
3. Installation 3.1 Mounting and Anchoring the Inverter and Integrated AC/DC Disconnect After you have determined a suitable location for the inverter/disconnect unit, the next step is anchoring the bracket to the wall stud(s). Models PVP1100, PVP2000, PVP2500, PVP2800, PVP3000 and PVP3500 1. Locate a wall stud in the desired location and align the mounting bracket or paper mounting template with the vertical row of screw holes over it for a single-stud mount.
6. Locate the inverter mounting hole below the power board (see Figure 3-3). Insert the mounting screw through the inverter and tighten securely. Models PVP4600, PVP4800 and PVP5200 1. Locate the wall studs in the desired location and align the mounting bracket or paper mounting template over the studs. Mark the mounting holes. Ensure that locations A and B in the following figure are aligned over two wall studs. 2. VERIFY THE BRACKET IS LEVEL. Ensure points A and B are aligned with the wall studs.
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual Inside Screw Figure 3-3 Inverter’s Inside Screw Below the Power Board Securing the Integrated AC/DC Disconnect When the inverter’s screws are completely installed, the Integrated AC/DC Disconnect also needs to be secured to the wall. 1. Make sure the AC/DC ON/OFF switch is in the OFF position. 2. Remove the screws around the edge of the disconnect’s front cover and remove the lid. 3.
NOTE: Do not proceed with making the electrical connections until the inverter/disconnect unit is properly mounted. ! ! WARNING: Shock hazard Do not remove the Integrated AC/DC Disconnect after it is installed. The AC/DC disconnect switch in the Integrated AC/DC Disconnect is compliant with UL 98. This is a non-serviceable component and needs to remain in place even during removal of the inverter. Removal of the Integrated AC/DC Disconnect can expose energized conductors.
4. Wiring Requirements 4.1 Electrical Connections The design intent of the PV Grid-tied Inverter and Integrated AC/DC Disconnect unit is to provide a safe method of connecting the inverter to the PV system array and the utility service source circuits. The AC/DC Disconnect provides a single location for terminating AC, DC and ground conductors.
! ATTENTION Toutes les installations électriques devraient être faites selon les codes de l’électricité locaux. Le Code national de l’électricité (NEC) exige que l’onduleur soit connecté à un circuit spécialisé sans aucun autre dispositif ou sortie connecté au même circuit. Voir le NEC à la section 690-64(b)(1). Le NEC impose également des restrictions sur la taille de l’onduleur et la manière dont il est connecté au réseau du service public. Voir le NEC à la section 690-64(b)(2).
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual Inverter Model PVP4600 Nominal Voltage 208VAC PVP4800 240VAC PVP5200 240VAC Grid Type 208VAC: 120V Wye Three Phase 240VAC: 120VAC Split Phase, 240VAC: 120VAC High Leg 240VAC: 120VAC Split Phase, 240VAC: 120VAC High Leg Table 4-1 Inverter Compatibility with Voltage and Grid 208VAC: 120V Wye Three Phase 240VAC: 120VAC Split Phase 240VAC: 120VAC High Leg Figure 4-1 Supported Utility Voltage Configura
4.4 AC Circuit Breaker Requirements The main utility service panel must dedicate a single- or multi-pole breaker to operate each installed 120/240/208 VAC PV Powered Inverter. This circuit breaker must be sized to handle the rated maximum output voltage and current of the inverter. To reduce the risk of fire, connect the inverter/disconnect unit to the appropriate size circuit breaker provided in Table 4-2.
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual Condition Line frequency low Factory Setting 59.3 Hz Maximum Trip Time(s) < 160ms 60.5 Hz < 160ms Line frequency high Table 4-3 Inverter Voltage and Frequency Limits ! ! WARNING Electrical connections must be completed in accordance with local electrical codes and the National Electrical Code (NEC), ANSI/NFPA 70. Use 12 AWG minimum, 90°C copper wire for all inverter electrical connections.
! AVERTISSEMENT Suivre l’ordre présenté ci-dessous pour connecter l’onduleur et le dispositif de déconnexion. L’inobservation de cet ordre peut causer des tensions dangereuses ou la déconnexion des contacts. IMPORTANT: When mounting the inverter/disconnect outside, use raintight or wet-location conduit hubs that comply with the requirements in the Standard for Fittings for Conduit and Outlet Boxes, UL 514B.
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual The three sections are: • • • Left knockouts — dedicated to the low voltage DC communications for the PVM1010 Data Monitoring Module Center knockouts — dedicated to AC connections Right knockouts — dedicated to DC connections Refer to the following figure for specific locations of the knockouts.
Maximum Current Rating 15 Minimum Size of Grounding Electrode Conductor AWG Copper Aluminum Copper Clad 8 6 20 8 6 30 8 6 40 8 6 60 8 6 Table 4-4 Grounding Electrode Conductor Sizing Disconnect Grounding The AC/DC Disconnect uses a single-point grounding connection, the grounding lug, providing continuity for both the EGC and GEC. The grounding lug is permanently bonded to the metal of the disconnect. The grounding lug is provided to facilitate the system ground bonding to the cabinet.
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual Grounding Schematic Figure 4-3 is a schematic representation of the PV Powered single-point grounding in the inverter. The front lid is grounded through the metal pem insert which accepts each screw securing the lid.
Inverter Cabinet Inverter Grounding Lug EGC Conductor PV GFI AC Ground Terminal GEC Conductor Disconnect Grounding Lug Disconnect Cabinet Figure 4-4 Grounding of the Inverter and Integrated AC/DC Disconnect Ground Fault Interruption Circuit (GFI) The purpose of the GFI circuit is to detect a ground fault current, interrupt the flow of a fault current and provide an indication of the fault. A ground fault is defined as “unintended current flow to ground” which presents a hazardous condition.
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual Figure 4-5 Ground Fault Message If the inverter displays “Ground Fault”, turn the AC/DC Disconnect OFF and refer to the fault information in Chapter 7. Integrated AC/ DC Disconnect AC Wiring Connections DC Wiring Connections AC Ground Terminal Grounding Lug Figure 4-6 AC and PV Grounding in Integrated AC/DC Disconnect Cabinet 4.
Model PVP1100 PVP2000 PVP2500 AC Line Input Terminal L1 L1 or L2 of 120VAC Split Phase Service L2 Neutral of 120VAC Split Phase Service L1 L1 of 240VAC: 120VAC Split Phase Service L2 L2 of 240VAC: 120VAC Split Phase Service L1 L1 of 240VAC: 120VAC Split Phase Service L2 L2 of 240VAC: 120VAC Split Phase Service L1 Phase A, B or C of 208VAC: 120V Wye Three Phase Service L2 Phase A, B or C of 208VAC: 120V Wye Three Phase Service L1 L1 of 240VAC: 120VAC Split Phase Service L2 L2 of 240VAC:
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual ! ! WARNING Ensure the main circuit breaker at the utility service panel is switched off before connecting to the AC terminal block. AVERTISSEMENT S’assurer que le disjoncteur principal du panneau de service public est déconnecté avant de le connecter au bloc de jonction en CA. To wire the inverter/disconnect unit to the main utility grid, follow these steps. 1.
NOTE: In the PVP1100 units the Line 1 conductor is the only phase voltage wire and Line 2 is neutral. Line 1 EGC Line 2 Figure 4-7 Disconnect’s AC Conductor Connections: EGC, Line 1 and Line 2 Connecting DC Conductors from the PV System Array The DC input terminals provided in the disconnect accept up to 6 AWG multi-stranded conductors from the PV system array.
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual AVERTISSEMENT ! S’assurer que le système de mise à la terre et la tension du panneau PV entre la borne positive et négative des connecteurs de câble des panneaux PV sont corrects avant de connecter les panneaux au bloc de jonction en CC sur le tableau de distribution de l’alimentation.
9. Ensure all connections are wired correctly, properly torqued and that there are no loose strands of wire. 10. Remove the 1A fuse from the external port on the inverter by unscrewing the cap housing the fuse. Refer to Figure 4-2 for the location of the fuse. 11. Confirm the AC/DC Disconnect is in the OFF position and remove the material covering the PV array. The PV array should now be exposed to sunlight, energizing the PV side of the system. 12.
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual Note: An exception exists if a dedicated PV system AC sub-panel is used to combine multiple inverters. The dedicated PV system AC sub-panel requires a single breaker at the main utility service panel for a multiple inverter installation.
Inverter #1 GND L1 L2/N Inverter #2 Pos Gnd Neg GND L1 L2/N Inverter #3 Pos Gnd Neg From Utility L1, L2 and EGC GND L1 L2/N Pos Gnd Neg From PV System Pos, Neg and GEC Figure 4-8 Wiring Multiple Arrays with Inverter/Disconnect Units To start the inverter/disconnect unit, see the next chapter Operation.
5. Operation ! Before turning on the inverter, ensure that the inverter and disconnect front covers are closed properly. AVERTISSEMENT ! Avant de mettre l’onduleur sous tension, s’assurer que les panneaux avant de l’onduleur et du dispositif de déconnexion sont adéquatement fermés. WARNING ! The heat sink can reach temperatures in excess of 158ºF (70ºC). Do not touch the heat sink when in use, and do not place anything on top of the heat sink.
! AVERTISSEMENT Avant de mettre l’onduleur et le dispositif de déconnexion CA/CC sous tension, s’assurer que le panneau avant est adéquatement fermé et que les vis du couvercle sont vissées. The green LED should illuminate. Locate the LEDs in the upper left hand corner of the inverter’s display. Verify that the red and green LED lights are illuminated. • • If the red LED is not illuminated or is blinking, refer to Chapter 6, Troubleshooting on page 33.
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual Red LED is illuminated when: • The PV array voltage is not within required operating limits, such as: • At sunset, when the inverter turns off for the night. • When clouds reduce the amount of available sunlight or when portions of the PV array are covered with debris. • • Any time the DC output from the PV array drops below the inverter’s minimum DC operating voltage, the inverter turns off.
Screen 1 Screen 2 Screen 3 Figure 5-2 Running Screens If a fault occurs, the display also provides a corresponding fault code. Refer to Chapter 6, Troubleshooting on page 33 for additional information.
6. Troubleshooting The inverter provides two indicator lights in the form of Light Emitting Diodes, or LEDs. The LEDs are the primary indicators of the system status: O.K., Sleep or Faulted. The LEDs are located above the inverter display in the upper left hand corner on the front lid. 6.1 LED Status • • • The light on the left is a red LED and is the primary indicator of system stand-by or fault condition. A solid red LED and a blank screen indicates the system is in normal sleep or stand-by mode.
3. A less likely cause is limited to multiple inverter installations, when the positive and negative array strings are crossed. Crossed wires occur when a positive or negative conductor from array 1 is connected with wires in array 2. An example is if inverter A has the positive conductor from array 1 and the negative conductor from array 2 connected. 4. If the fuse is open, then a ground fault condition exists. • Check the DC voltage between the grounded terminal of the array and earth ground.
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual Screen 1 Screen 2 Screen 1 Screen 2 Figure 6-2 Starting Up From a Faulted State NOTE: In this case the fault refers to the last fault detected. If the inverter is in a faulted state, the red LED blinks and the VFD scrolls through the screens shown in the faulted example above. The text of the fault describes the specific fault condition that the inverter experienced.
Figure 6-4 Power Low Fault Figure 6-4 shows a Power Low fault. After the fault occurrence, the inverter had a DC Voltage High fault. In this case, the display added the fault codes 0200 0000 plus 1000 0040 to become 1200 0040. If the faults have the same first digit (such as 1000 XXXX) the 1 remains the same and only the second block of four numbers add to the original fault code. ! ! WARNING These servicing instructions are for qualified personnel only.
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual Fault Code VFD Text Fault Description The grid frequency went below the limits in Table 4-3. The grid frequency went above the limits in Table 4-3.
Fault Code 1000 0002 1000 0001 0200 0000 0004 0000 0001 0000 Table 6-2 Normal Fault Codes If the following fault codes occur, please contact PV Powered Technical Support for service.
7. Service and Replacement PV Powered provides service guidelines for disconnecting and replacing an inverter. Always request and receive a replacement prior to separating the inverter from the Integrated AC/DC Disconnect assembly. PV Powered maintains an advanced replacement policy which provides qualified personnel with a similar inverter for immediate replacement of the unit being removed. In the unlikely event the inverter requires replacement, the disconnect remains in place.
These connections include: • AC connection terminal • DC connection terminal • External Ground Fault Interrupt fuse Review the following figure for the terminal locations. The inverter is connected to the electrical grid using three wires: Line 1, Line 2 and GEC.
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual 7.3 Replacing the Inverter 1. Remove the screws and the lid on the replacement inverter. 2. Place the replacement inverter on the mounting bracket. 3. Replace the three mounting screws in the lower section of the inverter assembly to secure the inverter to the mounting bracket. 4. Reinstall each of the fittings with their locking nuts in the knockouts for the conductors.
Note: The AC conductors are reversed when running from the disconnect to the inverter. For example, the EGC is the left terminal in the disconnect but is the right terminal in the inverter. 3. Ensure all connections are wired correctly and properly torqued as indicated on the Field Connections label inside the AC/DC Disconnect cabinet.
Appendix A - Specifications The specifications detailed below are expected operational parameters, and should be used in designing your PV system in accordance with the NEC. A.1 Inverter Specifications Specifications PVP1100 PVP2000 115VDC450VDC 115VDC380VDC 115VDC450VDC 115VDC380VDC 140VDC450VDC 140VDC380VDC 180VDC450VDC 180VDC380VDC 10A 18A 20A 18A 105.6V132.
Specifications PVP3000 PVP3500 170VDC450VDC 170VDC380VDC 18A 200VDC450VDC 200VDC380VDC 18A Maximum DC Input Voltage (VOC) DC Voltage Operating Range (V) DC MPPT Range (V) DC Imp Maximum Current (A) DC Isc Maximum Current (A) AC Operating Range (V) 500VDC 205VDC450VDC 205VDC380VDC 25A Power Factor AC Maximum Continuous Current(A) 240VDC450VDC 240VDC380VDC 25A 26A 211V183V264V 229V 59.3Hz-60.
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual A.2 Integrated AC/DC Disconnect Specifications Specification Value Switch orientation AC/DC ON AC/DC OFF 12 AWG, minimum 6 AWG maximum 194oF (90oC) copper wire Input/output wire sizes Max. DC voltage Max. DC current 500 VDC 48 ADC Max. continuous current > 26 ADC Max. AC voltage Max. AC current 600 VAC 40 AAC Number of terminals 3 positive/3 negative Enclosure type NEMA 3R Weight (lbs) 5 (2.
A.3 Circuit Breaker Requirements Inverter Model Circuit Breaker Required PVP1100 1 pole 15A PVP2000 2 pole 15A PVP2500 2 pole 20A PVP2800 2 pole 20A PVP3000 2 pole 20A PVP3500 2 pole 20A PVP4600 2 pole 30A PVP4800 2 pole 30A PVP5200 2 pole 30A Table A-3 Circuit Breaker Requirements A.4 Abnormal Specifications The specifications listed below are classified as abnormal and are not representative of normal operation.
Appendix B - Ground Configuration B.1 Field Configuration of an Inverter for Use with Positively Grounded PV Arrays If the inverter is: • Equipped with an Integrated AC/DC Disconnect, use the instructions in “Inverter with an Integrated AC/DC Disconnect”. Otherwise, if the inverter is: • Not equipped with an Integrated AC/DC Disconnect, skip to the section titled “Inverter without an Integrated AC/DC Disconnect”. Inverter with an Integrated AC/DC Disconnect 1.
Port J10 Note the reversal of the black and white conductors in the terminals from Figure B-1. Figure B-2 Conductors Reversed on Power Board Terminals 4. The text on the DC terminal circuit boards must now be covered with the following label so the text on the DC terminal circuit board is reversed. Figure B-3 New Label for DC Terminal Circuit Board 5. Affix the following label on the exterior of the AC/DC Disconnect.
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual GFI Negative Jumper Figure B-5 GFI Negative Jumper in J10 Port 6. Locate the pre-installed negative GFI jumper into port J10. Remove the negative jumper and replace with a positive ground jumper. Negative GFI Positive GFI Figure B-6 Negative and Positive GFI Jumpers ! WARNING Do not connect or disconnect the GFI jumper shown in Figure C-1 while the inverter is supplied with DC or AC power.
Inverter without an Integrated AC/DC Disconnect 1. Determine the polarity of DC conductors coming from the PV array. J10 Port with GFI Negative Jumper PVreceives DC+ from array PV+ receives DC- from array Figure B-7 PV Terminals in the Inverter 2. Install the DC positive conductor from the PV array into the PV positive (+) terminal on the inverter Power Board. 3. Install the DC negative conductor from the PV array into the PV negative (-) terminal on the inverter Power Board. 4.
Appendix C - Cabinet Dimensions C.
Figure C-2 Back and Bottom Views of PVP1100, PVP2000, PVP2500, PVP2800, PVP3000 and PVP3500 Inverter-only Cabinet 52
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual Figure C-3 Side and Front Views of the PVP4600, PVP4800 and PVP5200 Inverter-only Cabinet 53
Figure C-4 Back and Bottom Views of PVP4600, PVP4800 and PVP5200 Inverter-only Cabinet Inverter-only Cabinet 54
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual C.
Figure C-6 Back and Bottom Views of the PVP1100, PVP2000, PVP2500, PVP2800, PVP3000 and PVP3500 Inverter with Integrated AC/DC Disconnect Cabinet 56
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual Figure C-7 Side and Front Views of the PVP4600, PVP4800 and PVP5200 Inverter with Integrated AC/DC Disconnect Cabinet
Figure C-8 Back and Bottom Views of PVP4600, PVP
Limited Warranty Terms of Coverage The warranty period for the inverter is ten years, and the warranty on the data monitoring module is one year, each beginning on the date of purchase by the original end user.
• • • • • • • • Shipping or transportation damages. Improper installation. Improper maintenance. Excessive voltage or current conditions from the electrical grid or PV panels. Exposure to unsuitable environmental conditions (including but not limited to damage due to lightning strikes, storm, fire, flood, etc.). Unauthorized or abnormal use, repair, modification, or operation. Negligence or accidents. Material or workmanship not provided by PV Powered or its authorized service centers.
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual APPLICABLE LAW THEY ARE LIMITED TO THE DURATION OF THIS LIMITED WARRANTY. SOME STATES AND PROVINCES DO NOT ALLOW LIMITATIONS OR EXCLUSIONS ON IMPLIED WARRANTIES OR ON THE DURATION OF AN IMPLIED WARRANTY OR ON THE LIMITATION OR EXCLUSION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATION(S) OR EXCLUSION(S) MAY NOT APPLY TO YOU. THIS LIMITED WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS.
62
Return Procedure Before returning the product directly to PV Powered, you must first obtain a Return Materials Authorization Number (RMA) from PV Powered. When you contact a PV Powered representative, please have the following information ready: 1. The serial number of the product 2. The reason for the return 3. A copy of your dated proof of purchase On the packaging, please include the following: 1.
64
Index A abbreviations v AC breakers 14 circuit board 23 connections 40 grounding 17 reversed conductors 42 sub-panel 14, 27 wiring 21 wiring multiple inverters 27 acronyms v anchoring 7 B block diagram of system grounding 19 bracket 5, 7, 8, 9, 40, 41 C caution information about iii checking polarity 26 checking voltage 26 circuit breaker AC requirements 14 requirements 14, 46 circuits 16 clearances 5 conductor neutral (PVP1100) 41 reversing 41, 42 size 13, 15 stripping 13 conduit hubs 16 connecting inverte
inverter/disconnect unit anchoring 7 brackets 5 circuit breaker requirements 14 components 6 connecting to array 24 connecting to utility service 23 enclosure 5 energizing 26 locating 5 locking 30 mounting 5, 7 multiple installation of 14, 26, 27 service 11 starting 29 troubleshooting 33 ventilation 5 voltage frequency limits 14 wiring multiple 26 G GEC 17, 18 connecting 40 generating power 33 GFI 20 activating circuit 20 fuse type 34 ground fault 20, 29, 33 display 21 grounding field configuring 47 for mu
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual system disconnect 21 system ground 18 diagram of single-point 19 system voltage 26 O online string calculator 24 P polarity 29, 50 checking 24 reversed 26, 33 troubleshooting 31 power distribution board 40 power generation 33 PV array positive grounding 47 PV Powered how to contact i T temperature 25 terminals for conductors 39 terminating connections 11 timer on fault conditions 35 troubleshooting interfe
68
PV Grid-tied Residential Inverter and Integrated AC/DC Disconnect Installation and Operation Manual 69
70
PO Box 7348 • Bend, OR 97708 • P: 541-312-3832 • www.pvpowered.