Technical information

42
Note: TheACconductorsarereversedwhenrunningfromthe
disconnecttotheinverter.Forexample,theEGCistheleft
terminalinthedisconnectbutistherightterminalinthe
inverter.
3. Ensure all connections are wired correctly and properly torqued as
indicated on the Field Connections label inside the AC/DC Disconnect
cabinet.
AC Conductor
Connections
DC Conductor
Connections
Line 1 Line 2/N GND Grounding Lug
Figure 7-2 Reconnecting the Inverter’s Conductors
7.4 Finishing the Replacement
Replace the lids and the screws securing the lids for the inverter and the
disconnect.
!
WARNING
Before turning on the inverter and disconnect, ensure that the
front panel is closed properly and the lid’s screws are tightened.
!
AVERTISSEMENT
Avant de mettre l’onduleur et le dispositif de déconnexion sous
tension, s’assurer que le panneau avant est adéquatement fermé
et que les vis du couvercle sont vissées.
To start the inverter/disconnect unit the disconnect, see Chapter 5
Operations
on page 29.
+
-
GEC
DC Conductors,
from Disconnect,
Threaded through
Fitting
AC Conductors,
from Disconnect,
Threaded
through Fitting
}