Technical information
46
A.3 Circuit Breaker Requirements
Inverter Model Circuit Breaker Required
PVP1100 1 pole 15A
PVP2000 2 pole 15A
PVP2500 2 pole 20A
PVP2800 2 pole 20A
PVP3000 2 pole 20A
PVP3500 2 pole 20A
PVP4600 2 pole 30A
PVP4800 2 pole 30A
PVP5200 2 pole 30A
Table A-3 Circuit Breaker Requirements
A.4 Abnormal Specifications
The specications listed below are classied as abnormal and are not
representative of normal operation.
Abnormal Specications PVP1100 PVP2000 PVP2500 PVP2800
Momentary current transient
obtained during abnormal operation
100 A-pk /
0.58 ms
142 A-pk /
0.66 ms
88 A-pk
166 A-pk /
0.61 ms
Maximum input source backfeed
current to input source
0A
Abnormal Specications PVP3000 PVP3500 PVP4600 PVP4800 PVP5200
Momentary current transient
obtained during abnormal operation
166 A-pk /
0.61 ms
88 A-pk 88 A-pk 88 A-pk 88 A-pk
Maximum input source backfeed
current to input source
0A
Table A-4 Abnormal Specifications