5975190EN (05/2015) 1060-00 Lifting Station Type ABS Nirolift Lifting Station Type ABS Sanisett EN Installation and Operating Instructions www.sulzer.
Installation and Operating Instructions Lifting Station Type ABS Nirolift. Lifting Station Type ABS Sanisett. Lifting Station Type ABS Nirolift Lifting Station Type ABS Sanisett Contents 1 General.................................................................................................................................................... 3 1.1 Description..............................................................................................................................................
Installation and Operating Instructions 3 Lifting Station Type ABS Nirolift. Lifting Station Type ABS Sanisett. 1 General 1.1 Description The wastewater lifting stations Nirolift and Sanisett consist of a synthetic collection tank which is waterproof in accordance with EN 12050-2, together with a cover plate with odour-preventing filter and lockable floor inlet. The Sanisett is supplied with a junction piece for the discharge line and a bracket for the level control.
Installation and Operating Instructions Lifting Station Type ABS Nirolift. Lifting Station Type ABS Sanisett. 1.3 Legal regulations covering the use of lifting stations for the pumping of faecal-free effluent. Automatically operated lifting stations are required if: -- the water level in the odour lock of the effluent source lies below the sewer backwash level. -- rainwater gullies are present where the upper edge of the inlet grid lies below the sewer backwash level.
Installation and Operating Instructions 5 1061-01 Lifting Station Type ABS Nirolift. Lifting Station Type ABS Sanisett.
Installation and Operating Instructions Lifting Station Type ABS Nirolift. Lifting Station Type ABS Sanisett. 5 Set-up and Installation 5.1 Installation of the collection tank Set the collection tank on a bed of sand, in a frost-free area, in the prepared opening of approximate dimensions 755 x 600 x 750 mm for Nirolift and 1100 x 900 x 850 mm for Sanisett, and ensure that it is horizontal in all directions.
Installation and Operating Instructions 7 Lifting Station Type ABS Nirolift. Lifting Station Type ABS Sanisett. 5.5 Mounting of the upper fitting 1. Insert the white plastic installation cover (a) into the frame of the upper fitting. The cover is only suitable for foot traffic (see Figure 4). 2. Adjust the upper fitting in the tank opening until the edge of the rim is level with the finished floor. The rim should also be parallel with the wall or floor tiles. 3.
Installation and Operating Instructions Lifting Station Type ABS Nirolift. Lifting Station Type ABS Sanisett. 5.7 Location of power supply cable and float switch The connection cable for the pump is fed through the cable pipe and brought into the room where the power supply is located by means of a branch pipe (T-piece). The connection cable is fed through the slot in the cable inlet and the cable inlet itself is pushed firmly into the branch pipe.
Installation and Operating Instructions 9 Lifting Station Type ABS Nirolift. Lifting Station Type ABS Sanisett. 7 Maintenance c c To avoid danger if the power cable is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person. Before commencing any maintenance work the unit should be completely disconnected from the mains by a qualified person and care should be taken that it cannot be inadvertently switched back on.
Installation and Operating Instructions Lifting Station Type ABS Nirolift. Lifting Station Type ABS Sanisett.
Installation and Operating Instructions Lifting Station Type ABS Nirolift. Lifting Station Type ABS Sanisett.
Sulzer Pump Solutions Ireland Ltd. Clonard Road, Wexford, Ireland Tel. +353 53 91 63 200. Fax +353 53 91 42335. www.sulzer.