Specifications
22 
Figure 12 - Charging Stages 
Permission Pending 
With the general understanding of what to look for in a charging circuit we can now look 
to  see  how  the  specified  battery  will  react  to  the  previously  discussed  charging 
methods. The battery chosen with a capacity of thirty eight amp/hour would then have a 
bulk charge state of one hour and thirty minutes with an average charge of twenty five 
amps  to  bring  the  battery  from  zero  percent  capacity  through  the  bulk  stage  of  the 
charging process to around ninety percent capacity. Because of the fickle nature of the 
generators as they are  dependent on ever changing variables the charge time of the 
generator deployed outside in the elements would also have to take into account the 
changing charging amperages as well as temperature of the surrounding environment 
and could greatly fluctuate with a multitude of given circumstances. After the charging 
current falls below one amp in this state the charging circuit will have to switch over to a 
constant current of two amps for one hour to complete the charge. 
The voltage on the battery at this point should be around fourteen volts and will be a 
satisfactory cut off point for the charging circuit. Because the battery will be stored in the 
generator for a long period of time a float stage will also be beneficial to the charging 
circuit to combat the self-depletion of the battery. This will allow the battery to be stored 
close to full capacity and will be beneficial squeezing as much life out of the battery as 
possible until  it will need to be replaced.  The charging  circuit will  also call  for an 
equalization  stage  in  the  process  where  a  current  of  two  amps  was  applied  to  the 
battery for an hour in order to equalize all batter cells in the specified battery. 










