Installation manual

5
1.4
Technical Specifications
MODEL PDSP3120 PDSP3160
Output (kVA) 120 160
Output (kW) 96 128
Output Power Factor 0,8
INPUT
Number of Phases 3 Phase + Neutral
Input Voltage 220/380 Vac , 230/400Vac or 240/415Vac 3phase+N
Input Voltage Tolerance +20%,-25% (+15% , -30% for 240/415Vac)
Input Power Factor (PF) 0,99 (at full load)
Input THDI 5 % (at full load)
Input Frequency 50Hz ± 5 %
By-pass Voltage 220/380 Vac , 230/400Vac or 240/415Vac 3phase+N
By-pass Frequency 50Hz
By-pass Frequency Tolerance (± 2 % )
RFI Level EN50091
Split By-pass Connection Available
OUTPUT
Number of phases 3 Phase + Neutral
Output Voltage 220/380 Vac , 230/400Vac or 240/415Vac 3phase+N
Output Voltage Tolerance ± 1 %
Output Frequency 50 Hz
Output Frequency Tolerance (line synchron) (± 2 % )
Output Frequency Tolerance (free running) ± 0,2 %
Efficiency (at full linear load) up to 94 %
Load Crest Factor 3 : 1
Output Voltage THD 3 %
Overload 125% Load 10min. , 150% Load 1min.
BATTERIES
Total Number
60 (2x30) pieces 12V
Float Charge Voltage (25
0
C)
± 405 Vdc
End of Discharge Voltage
± 300 Vdc
Battery Test
Automatic and Manual
Boost Charge
Available
INTERFACE
RS 232 comm. Port
Standard (Optional port multiplexer available)
RS 485 comm. Port
Optional
Remote Monitoring Panel
Optional
SNMP Adapter
Optional
Modbus Adapter
Optional
Alarm Relay Contacts
3x Dry Relay Contacts
(Line failure, battery low, bypass)
EPO Input
Standard
ENVIRONMENT
Operating Temperature 0 – 40
0
C
Operating Humidity
< 90% (Non-Condensing)
Acoustic Noise
<70 dB
Dimensions (HxWxD) (mm)
1900 x 780 x 890
Protection Class
IP20
Weight (Without Batteries) (approx. kgs)
375 425