5.20.3 Test Control 
Any input may be placed on ‘soak test’ to prevent it from generating an alarm. If the input triggers 
whilst the system is armed, it will indicate the activation and enter the details in the system log. You 
can also enter the number of days you would like the soak test to last, after this period the inputs 
will be active. 
5.20.4 Test Bell 
Any outputs programmed as Any Siren or Any Strobe will be activated in this test. 
5.20.5 Do Battery Load Test 
Battery Test 
The system performs a check of the battery operation every 10 seconds, by dipping the power 
supply voltage momentarily, and measuring the system voltage. If the battery voltage measured is 
below 12.0V, or the battery fuse has failed, a ‘BATTERY FAULT 100’ warning will be generated. 
Battery Load Test
PCX Systems may be programmed to perform an automatic battery load test at every power 
supply at 07.00am each day. This will drop the power supply voltage below the battery voltage, 
whilst monitoring the system diagnostics. 
The test will NOT take place if: 
¾ The End Station bell and strobe PGMs are live 
¾ The system is in Engineer Mode 
¾ Any battery faults exists 
¾ Any mains fault exists 
¾ The site option is not selected 
If the test has already started, it will be aborted if any of these conditions apply, other than entry 
into Engineer Mode. If the test is aborted, it will NOT be performed until the next day. 
This is selected in SITE OPTIONS under “Do Battery Load Test”. The test may also be performed 
as required, under engineer control. 
5.20.6 Test PGMs 
The engineer can test all the Programmable Outputs on the End Station and the ROX’s. This test 
can also be used to test the ATE pins, all you need to do is select the outputs you have chosen for 
the pins and test them, the signal will be then sent out on both the programmable outputs and the 
ATE pins. 
Please note that some ARC’s require that you signal events continuously, therefore ‘Force Arm On 
1
st
 Input’ should be used. Please see page: 12 
5.20.7 Test PHC Communications 
Before SMS signalling can be used, it must be initialised by communication with the Pyronix Host 
Computer (PHC). Once the test has completed, SMS texting can be performed. 
PLEASE NOTE ALL PHC CALLS COST 50p PER CALL 