Version 6.41
3. Install HX NC ROMs
If you have HX Node Controllers, you must remove and replace the
ROM ICs containing the application. HX Node Controllers do not have
FLASH ROM and therefore are not programmed using the procedure
for Series 7000 Node Controllers.
Note After replacing the Horizon Node Controller’s ROMs, the mod-
ules must be cold-started using this unique procedure: remove
the module from the frame, and re-insert it while holding in the
cold-start push-button located at the top of the module. Contin-
ue to push the button in until the red ERR LED goes off.
Load Control Panel and UMD Software
This is to be used when upgrading from all versions.
At the system terminal enter the following command:
SMS7000> inputfrom “progcp.red”
After typing the command above, the system sequentially programs each
panel of the corresponding type.
Note The default application loaded into the Client panel is cln.mot.
If you want to load clf.mot application software for Client
Former functionality, use
sms7000>prog “clf.mot” cp cln
after running the batch file “progcp.red”.
The panels/umds display the string download with a rotating | in the last
character position to indicate a download is in process. Other functions are
not accessible from the keyboard until the download is complete.
After programming, check each panel's revision string. This is done at
the terminal using the following command:
Also, confirm the software version loaded into each panel. To do so, on
panels with a dedicated ID button, a single ID button press initiates the
ID function. In most other panels, however, four consecutive presses
are needed to initiate the ID sequence.
Table 15. Horizon Node Controller Firmware
Description
Quantity
per
Board
Firmware
Part Number
Board(s)/ Part Number
HX NC ROM(U17) 1 151109-05 HX Node Controller/062797-01
HX NC ROM(U18) 1 151108-05 HX Node Controller/062797-01
SMS7000> ver cp OR SMS7000> ls cp