Owner`s manual

Page 14
7039-131I
February 20, 2011
2100 Millennium Wood Stove (ACC)
NOTE: In Canada when using a factory-built chimney it must
be safety listed, Type UL103 HT (2100
o
F) CLASS “A” or
conforming to CAN/ULC-S629M, STANDARD FOR 650
o
C
FACTORY-BUILT CHIMNEYS.
5
Chimney Requirements
Floor
Protector
Thimble,
12" (305mm)
Of Brick
Ceiling Joist
Combustible Wall
Airtight
Cleanout Door
Fireclay Flue Liner
With Air Space
Sheathing
Eave
1" (25mm) Clearance
With Firestop
Rafter
Flashing
Concrete Cap
Outside Air
Termination Cap
Outside Air Rear Vent
Spark Arrestor Cap
Floor
Protector
Chimney
Connector
Ceiling Support
Listed Chimney
Listed Termination Cap
Storm Collar
Flashing
Figure 14.1 Prefabricated Exterior Chimney
Figure 14.2 - Prefabricated Interior Chimney
A. Venting Components
Chimney Connector:
It is also known as ue pipe or stove pipe. The chimney
connector joins the stove to the chimney. It must be a 6 inch
(152mm) minimum diameter 24 gauge mild steel black or
26 gauge blued steel, or an approved air-insulated double
wall venting pipe.
Thimble:
A manufactured or site-constructed device installed in
combustible walls through which the chimney connector
passes to the chimney. It is intended to keep the walls
from igniting. Site constructed thimbles must meet
NFPA 211 Standards. Prefabricated must be suitable
for use with selected chimney and meet UL103 Type HT
Standards. Follow instructions provided by the manufacturer
for manufactured thimbles for masonry chimney and
prefabricated chimneys.
Chimney:
The chimney can be new or existing, masonry or prefabricated
and must meet the following minimum requirements specied
in Section 5B.
B. Chimney Systems
Must be minimum 6 inch (152mm) diameter (ID) high
temperature chimney listed to UL 103 HT (2100
o
F) or
ULC S629M.
Must use components required by the manufacturer for
installation.
Must maintain clearances required by the manufacturer
for installation.
Refer to manufacturers instructions for installation.
Prefabricated Metal Chimney