Installation manual

Quadra-Fire • TOPAZ-MBK-IPI, TOPAZ-D-PMH-IPI, TOPAZ-D-MBK-IPI, TOPAZ-D-CSB-IPI Installation Manual • 2341-980_R4 • 11/1440
E. Vertical Termination Requirements
InstallMetalRoofFlashing
 


     

Roof Pitch H (Min.) Ft.





 
 
 
 
 
 
 

HORIZONTAL
OVERHANG
VERTICAL
WALL
GAS DIRECT VENT
TERMINATION CAP
12
X
ROOF PITCH
IS X/ 12
LOWEST
DISCHARGE
OPENING
2 FT.
MIN.
20 INCHES MIN.
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
Figure7.11MinimumHeightFromRoofToLowestDischargeopening
NOTICE: Failure to properly caulk the roof ashing and pipe
seams may permit entry of water.
 

 

 

CAULK
Ceiling Firestop
Nails
Minimum 1 in.
(25mm) Clearance
Minimum 1 in.
(25mm) Clearance
Minimum 1 in.
(25mm) Clearance
Minimum 1 in.
(25mm) Clearance
Figure7.13
Figure7.12
 



WARNING! Risk of Fire! Maintain air space clearance to
vent. DO NOT pack insulation or other combustibles around
vent system. Failure to keep insulation or other material
away from vent pipe may cause overheating and re.