Specifications

Chapter 1. General description 3
Draft Document for Review May 12, 2014 12:46 pm 5102ch01.fm
Table 1-1 Operating environment for Power S822
1.3 Physical package
Table 1-2 shows the physical dimensions of the Power S822 chassis. The server is available
only in a rack-mounted form factor and takes 2U (2 EIA units) of rack space.
Table 1-2 Physical dimensions
Power S822 operating environment
Description Operating Non-operating
Temperature Allowable: 5 - 35
a
degrees C
(41 - 95 degrees F)
Recommended: 18 to 27 degrees C
(64 to 80 degrees F)
a. Heavy workloads may see some performance degradation above 35C if internal temperatures
trigger a CPU clock reduction.
5 - 45 degrees C
(41 - 113 degrees F)
Relative humidity 8 - 80% 8 - 80%
Maximum dew point 28 degrees C (84 degrees F) N/A
Operating voltage 200 - 240 V AC N/A
Operating frequency 47 or 63 Hz N/A
Power consumption 1810 Watts maximum N/A
Power source loading 1.88 kVA maximum N/A
Thermal output 6176 BTU/hour maximum N/A
Maximum altitude 3,050 m
(10,000 ft)
N/A
Noise level and sound power 6.7 bels operating; 6.7 bels idling N/A
Tip: The maximum measured value is expected from a fully populated server under an
intensive workload. The maximum measured value also accounts for component tolerance
and operating conditions that are not ideal. Power consumption and heat load vary greatly
by server configuration and utilization. Use the IBM Systems Energy Estimator to obtain a
heat output estimate based on a specific configuration, available at the following website:
http://www-912.ibm.com/see/EnergyEstimator
Dimension Power S822 (8284-22A)
Width 443 mm (17.5 in)
Depth 755 mm (29.7 in)
Height 87 mm (3.5 in)
Weight (maximum configuration) 28.6 kg (63 lbs)