Specifications
Chapter 1. General description 17
Draft Document for Review May 12, 2014 12:46 pm 5102ch01.fm
Table 1-8 shows the available wall power cord options for the PDU and iPDU features, which
must be ordered separately.
Table 1-8 Wall power cord options for the PDU and iPDU features
The Universal PDUs are compatible with previous models.
To better enable electrical redundancy, each server has two power supplies that must be
connected to separate PDUs, which are not included in the base order.
For maximum availability, a highly desirable approach is to connect power cords from the
same system to two separate PDUs in the rack, and to connect each PDU to independent
power sources.
For detailed power requirements and power cord details about the 7014 racks, see the
Planning for power section in the IBM Power Systems Hardware Information Center website:
http://pic.dhe.ibm.com/infocenter/powersys/v3r1m5/topic/p7had/p7hadrpower.htm
For detailed power requirements and power cord details about the 7965-94Y rack, see the
Planning for power section in the IBM Power Systems Hardware Information Center website:
http://pic.dhe.ibm.com/infocenter/powersys/v3r1m5/topic/p7had/p7hadkickoff795394x.
htm
Feature
code
Wall plug Rated
voltage (Vac)
Phase Rated
amperage
Geography
6653 IEC 309,
3P+N+G, 16A
230 3 16
Amps/Phase
Internationally available
6489 IEC309
3P+N+G, 32A
230 3 32
Amps/Phase
EMEA
6654 NEMA L6-30 200-208, 240 1 24 Amps US, Canada, LA, Japan
6655 RS 3750DP
(watertight)
200-208, 240 1 24 Amps US, Canada, LA, Japan
6656 IEC 309,
P+N+G, 32A
230 1 32 Amps EMEA
6657 PDL 230-240 1 32 Amps Australia, New Zealand
6658 Korean plug 220 1 30 Amps North and South Korea
6492 IEC 309,
2P+G, 60A
200-208, 240 1 48 Amps US, Canada, LA, Japan
6491 IEC 309,
P+N+G, 63A
230 1 63 Amps EMEA
Notes: Ensure that the appropriate power cord feature is configured to support the power
being supplied. Based on the power cord that is used, the PDU can supply from 4.8 kVA to
19.2 kVA. The power of all the drawers plugged into the PDU must not exceed the power
cord limitation.
Redundant power supplies: The second power supply for the Power S822 server is
optional and not included in the base order.