User's Manual

Quantum|ATL 7100 Series Library Unpacking Instructions
Document 6241100-03, Ver. 3, Rel. 1
August 2001
Selecting an Installation Location 5
Floor Strength,
Inclination, and
Characteristics
0
The floor at the installation site must be rated at 250 lb/ft
2
(1221 kg/
m
2
). This is sufficient to support a fully loaded Quantum|ATL 7100
Series library.
The floor must be level to within 0.25 inch (6.4 mm) over a 6-foot-by-6-
foot (1.83-meter-by-1.83-meter) area.
The floor at the installation site must be uncarpeted and free of defects.
Power and Grounding0
The power inlet is an IEC-320 connector (see figure 3). Outside North
America, replace the power cord with a harmonized 3 x 2 mm
2
power
cord that is approved by the country where used.
Figure 3 Library Power
Receptacle
Environmental
Conditions
0
The installation site must have the following environmental
conditions:
Humidity: 10% to 90%
Temperature: 15° C to 32° C (59° F to 90° F)
Altitude: sea level to 13,200 feet (4.023 km)
These environmental conditions only apply when the library is in
operation.
Caution: To prevent equipment damage, connect the library to a
grounded electrical outlet.
Note: For additional library specifications (including
environmental requirements during shipping and storage),
refer to the Quantum|ATL 7100 Series Library Facilities Planning
and Installation Guide.
Neutral
Line
Ground
IEC-320 Type
~100-120V/~200 - 240V
3.5A/7A 50/60 Hz
4A/2A