Specifications
BACnetT‐StatUser’sManualRev1.1,7/28/11 Page|3
Analog Input Object Detail 
Supported Properties  Writable?  Property Range Restrictions 
Object Identifier  N  N/A 
Object Name  N  N/A 
Description N N/A 
Object Type  N  N/A 
Present Value  N  N/A 
Status Flags  N  N/A 
Event State  N  N/A 
Out of Service  N  N/A 
Units N N/A 
Instance Description Writable?  Notes 
AI-0  Raw Zone Temp  N  Fahrenheit or Celsius reading of the zone thermistor, directly from 
the sensor (no offsets applied). 
A reading of -25F indicates an open sensor condition and a reading 
of 150F indicates a shorted sensor condition. 
AI-1  Raw Supply Air  N  Fahrenheit or Celsius reading of the supply air thermistor, directly 
from the sensor (no offsets applied). 
A reading of -25F indicates an open sensor condition and a reading 
of 150F indicates a shorted sensor condition. 
Analog Value Object Detail 
Supported Properties  Writable?  Property Range Restrictions 
Object Identifier  N  N/A 
Object Name  N  N/A 
Description N N/A 
Object Type  N  N/A 
Present Value  Y (some)  Y 
Status Flags  N  N/A 
Event State  N  N/A 
Out of Service  N  N/A 
Units N N/A 
Instance Description Writable? Units Limits Default  Notes 
AV-0  MAC Address  Y  None  1..127  1  MS/TP MAC address needs to be 
unique in each network. You should 
restart the unit after changing the 