Specifications
BACnetT‐StatUser’sManualRev1.1,7/28/11 Page|4
Instance Description Writable? Units Limits Default  Notes 
address. 
Note that the device object id is the 
MSTP Network * 1000 + the MAC 
address. 
AV-1  MSTP Network  Y  None  0..4194  0  MS/TP Network address should be 
unique for each network. You 
should restart the unit after changing 
the address. 
Note that the device object id is the 
MSTP Network * 1000 + the MAC 
address. 
AV-2 Zone Offset  Y TempF or 
TempC 
-9F..9F  0  Added to AI-0 (Zone sensor) to 
create AV-19 (Zone Reading). Use 
this number to calibrate your 
system. 
AV-3 Supply Offset  Y TempF or 
TempC 
-9F..9F  0  Added to AI-1 (Supply sensor) to 
create AV-20 (Supply Reading). Use 
this number to calibrate your 
system. 
AV-4  Residual Fan Delay  Y  Seconds  0..180  30  Number of seconds to let the fan 
continue running after the system 
reaches setpoint. 
AV-5  Occupied Cool Spt  Y  TempF or 
TempC 
42F..90F  74F  Occupied stage 1 cooling setpoint. 
AV-6  Unoccupied Cool Spt  Y  TempF or 
TempC 
42F..90F  85F  Unoccupied stage 1 cooling setpoint.
AV-7  Occupied Heat Spt  Y  TempF or 
TempC 
40F..88F  68F  Occupied stage 1 heating setpoint. 
AV-8  Unoccupied Heat Spt  Y  TempF or 
TempC 
40F..88F  55F  Unoccupied stage 1 heating setpoint.
AV-9  Cool 2 Stage Delta  Y  TempF or 
TempC 
1F..9F  2F  Degrees above the stage 1 cooling 
setpoint where stage 2 energizes. 
AV-10  Heat 2 Stage Delta  Y  TempF or 
TempC 
1F..9F  2F  Degrees below the stage 1 heating 
setpoint where stage 2 energizes. 
AV-11  Cool Heat Min Diff  Y  Seconds  2F..9F  4F  The minimum difference between 
stage 1 heating and cooling 
setpoints. Note that the system will 
automatically adjust the stage 1 
cooling setpoint to enforce this limit.
AV-12  Cool Min On Time  Y  Seconds  60..600  120  The minimum time that a cooling 
stage must be on before the system 
will change from that particular 
stage. 
AV-13  Cool Min Off Time  Y  Seconds  60..600  120  The minimum time that a cooling 
stage must be off before the system 
will change into that particular 