Specifications
BACnetT‐StatUser’sManualRev1.1,7/28/11 Page|8
Instance Description Writable? Units Limits Default  Notes 
window. 
Set both the Start and End values to 
0 to mark this window as unused. 
AV-51  Sun Sched Win 2 Start  Y  Minutes  0..1440  0  Number of minutes since midnight 
to begin occupied mode for this 
window. 
AV-52  Sun Sched Win 2 End  Y  Minutes  0..1440  0  Number of minutes since midnight 
to end occupied mode for this 
window. 
Set both the Start and End values to 
0 to mark this window as unused. 
AV-53  Curr User Spt Adjust  Y  TempF or 
TempC 
0..AV16  N/A  The current setpoint offset a user has 
entered via the front panel. 
AV-54  Front Panel Code  Y  None  0,11..99  0  The access code a user must enter to 
use the front panel programming 
menu. 
Binary Input Object Detail 
Supported Properties  Writable?  Property Range Restrictions 
Object Identifier  N  N/A 
Object Name  N  N/A 
Description N N/A 
Object Type  N  N/A 
Present Value  N  N/A 
Status Flags  N  N/A 
Event State  N  N/A 
Out of Service  N  N/A 
Polarity N N/A 
Instance Description Writable?  Notes 
BI-0  Fan Proof  N  The current reading of the fan proof input. 
Binary Value Object Detail 
Supported Properties  Writable?  Property Range Restrictions 
Object Identifier  N  N/A 
Object Name  N  N/A 
Description N N/A 
Object Type  N  N/A 