Specifications
BACnetT‐StatUser’sManualRev1.1,7/28/11 Page|9
Supported Properties  Writable?  Property Range Restrictions 
Present Value  Y (Priority array not available)  N/A 
Status Flags  N  N/A 
Event State  N  N/A 
Out of Service  N  N/A 
Polarity N N/A 
Instance Description  Writable?  Default  Notes 
BV-0  Temperature Units  Y  0  0 – Use Fahrenheit 
1 – Use Celsius 
BV-1  Occupied Fan Mode  Y  0  0 – Fan mode auto 
1 – Fan mode always on 
BV-2  Unoccupied Fan Mode  Y  0  0 – Fan mode auto 
1 – Fan mode always on 
BV-3  Force Occupied Mode  Y  N/A  0 – Remove BACnet occupied 
override 
1 – Enable BACnet occupied 
override 
BV-4  Zone Sensor Location  Y  0  0 – Use onboard zone thermistor 
1 – Use remote mounted zone 
thermistor 
Binary Output Object Detail 
Supported Properties  Writable?  Property Range Restrictions 
Object Identifier  N  N/A 
Object Name  N  N/A 
Description N N/A 
Object Type  N  N/A 
Present Value  Y*  N/A 
Status Flags  N  N/A 
Event State  N  N/A 
Out of Service  N  N/A 
Polarity N N/A 
Priority Array  Y*  N/A 
* - The binary output object utilizes the priority array 1 through 16. A BACnet client can see the system's output 
desire at priority 16 and is free to write any of the other 15 priorities. 
Instance Description  Writable?  Notes 
BO-0  Output G  Y  0 – De-energize Output 
1 – Energize Output 