Specifications
BACnetT‐StatUser’sManualRev1.1,7/28/11 Page|10
Instance Description  Writable?  Notes 
255 – Remove bypass 
BO-1  Output Y1  Y  0 – De-energize Output 
1 – Energize Output 
255 – Remove bypass 
BO-2  Output Y2  Y  0 – De-energize Output 
1 – Energize Output 
255 – Remove bypass 
BO-3  Output W1/B  Y  0 – De-energize Output 
1 – Energize Output 
255 – Remove bypass 
BO-4  Output W2  Y  0 – De-energize Output 
1 – Energize Output 
255 – Remove bypass 
BO-5  Output O  Y  0 – De-energize Output 
1 – Energize Output 
255 – Remove bypass 
Multistate Input Object Detail 
Supported Properties  Writable?  Property Range Restrictions 
Object Identifier  N  N/A 
Object Name  N  N/A 
Description N N/A 
Object Type  N  N/A 
Present Value  Y (some)  Y 
Status Flags  N  N/A 
Event State  N  N/A 
Out of Service  N  N/A 
Number of States  N  N/A 
Instance Description  Writable?  Limits Default  Notes 
MI-0  Baud Rate  Y  1..5  3  1 – 9600 Baud 
2 – 19200 Baud 
3 – 38400 Baud 
4 – 57600 Baud 
5 – 76800 Baud 
MI-1  HVAC Type  Y  1..6  1  1 – Single Stage Conventional 
2 – Dual Stage Conventional 
3 – Heat Pump 1 
4 – Heat Pump 2 
5 – Gas Heat 1 
6 – Gas Heat 2 