Technical data
100 •  BACnet/IP Controller 750-830 
  Programming the PFC Using WAGO-I/O-PRO CAA 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
3.1.8.4.1  IEC Task Sequence 
1. Determine the system time (tStart). 
2. If no full internal bus cycle has run since the last time the outputs were 
written: 
! Wait until the next internal bus cycle is completed. 
3. Reading of inputs and reading back of the outputs from the process image. 
4. If the application program has been started. 
! Execute the program codes for this task. 
5.  Writing of the outputs to the process image. 
6.  Determine the system time (tEnd). 
! tEnd - tStart = runtime for the IEC task 
3.1.8.4.2  Overview of Most Important Task Priorities 
Internal bus task/fieldbus task (internal) 
The internal bus task matches the process image to the input/output data of the 
modules in defined cycles. 
The fieldbus tasks are performed as triggered by events and only require com-
puting time when communication is performed via fieldbus (MODBUS). 
Normal task (IEC tasks 1-10) 
IEC tasks with this priority may be interrupted by the internal bus tasks. 
Therefore, configuration for the connected modules and communication via 
fieldbus with the watchdog activated for the task call interval must be taken 
into account here. 
PLC-Comm task (internal) 
The PLC-Comm task is active when logged in and takes up communication 
with the WAGO-I/O-PRO CAA gateway. 
Background task (IEC tasks 11-31) 
All internal tasks have a priority higher than that for the IEC background 
tasks. These tasks are therefore very well suited for performing time-intensive 
and non-critical time tasks, such as calling up functions in the SysLibFile.lib. 