Technical data
118 •  BACnet/IP Controller 750-830 
  Programming the PFC Using WAGO-I/O-PRO CAA 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
BACnet 
You can set the transmission rate of the internal data bus and the UDP port on 
the "BACnet" page. 
In the "UDP Port" field, enter the UDP port for BACnet/IP that is to be used. 
If you place a check mark in the "Non-adaptive internal data bus transmission 
rate in ms" box (default setting), the transmission rate will be constant and 
will not be adapted to the node configuration. 
This not only helps reduce the run-up time, but it also reduces the transmission 
rate. Remove the check mark to increase the transmission rate. 
Abb. 3-18: Web-based Management System: BACnet   